OLFLEX EB CY Control Cable

OLFLEX EB CY Control Cable
Details:
OLFLEX EB CY screened PVC control cable for type-i intrinsically safe circuits: tinned copper braid, sky-blue RAL 5015 jacket, IEC 60079-14 compliance, UV resistant to ISO 4892-2.

Standards & Compliance
IEC 60079-14:2013 / EN 60079-14:2014 §16.2.2 | VDE 0165-1 | EN 50525-2-51 | ISO 4892-2 (UV) | IEC 60332-1-2

Quick Specs
300/500 V (Ex-i) | 3000 V AC | 0.75 – 1.5 mm², 2 – 25 cores | −40 °C to +80 °C fixed
Send Inquiry
Download
Overview
Technical Specifications
Part Numbers
Part Number & specification Verification | Availability & Lead Time Confirmation

Xiamen Kabasi Electric Co., Ltd. is one of the most reliable manufacturers and suppliers of olflex eb cy control cable in China. If you're going to buy bulk durable cables made in China, welcome to get pricelist from our factory. All customized cables are with high quality and competitive price.

 

Lead Paragraph

 

OLFLEX EB CY is the screened, sky-blue PVC control cable for type-i intrinsically safe circuits in hazardous industrial atmospheres. It is built to IEC 60079-14:2013 / EN 60079-14:2014 / VDE 0165-1:2014 clause 16.2.2, and the sky-blue sheath at approximately RAL 5015 keeps a type-i circuit distinguishable from power wiring along the whole route. A tinned copper braid sits over a plastic foil wrap, giving high braid density and a transfer impedance of 250 Ω/km or less at 30 MHz; the jacket is UV and weather resistant to ISO 4892-2. KABASI supplies bulk lengths or finished harnesses terminated to your schedule.

 

Select Your Variant

 

Screened vs. Unshielded: OLFLEX EB CY vs. OLFLEX EB

Engineering Evaluation Factor

OLFLEX EB CY (Screened)

OLFLEX EB (Unshielded)

Selection Recommendation

Shielding Architecture

Tinned copper wire braided screen

None (bare core lay-up under outer sheath)

Specify EB CY where an IS loop shares a tray or raceway with drives or power cables.

Mutual Capacitance (Core/Core)

160 nF/km

140 nF/km

160 nF/km against 140 nF/km on the unshielded version; both figures enter the loop calculation against the barrier's C_o.

Core-to-Screen Capacitance

250 nF/km

Not applicable (no screen)

In high-noise petrochemical areas, the 250 nF/km, used in the loop calculation whenever the screen is bonded.

Outer Diameter & Weight

Slightly larger (e.g. 7 X 0.75 is 8.3 mm, 168 kg/km)

Slimmer (e.g. 7 X 0.75 is 6.7 mm, 81 kg/km)

Specify EB where space and barrier limits dominate; Specify EB where space and weight dominate; EB CY where the route carries drives or inverters.

Outdoor & Weather Resistance

Yes, UV resistant to ISO 4892-2

Yes, UV resistant to ISO 4892-2

Both versions are rated UV and weather resistant to ISO 4892-2.

 

 

Typical Applications

 

01petrochemical-refining-and-gas-processing-distillation-column-and-cooling-tower-lit-up-at-night-in-a-refinery-complex

Petrochemical Refining & Gas Processing
Type-i intrinsically safe loops - Signal circuits in a protected type-i installation, which is the application stated for this cable.

02offshore-platform-and-tank-farm-telemetry-deck-crew-in-coveralls-beside-a-lifeboat-station-and-radio-mast-at-sea

Offshore Platform & Tank Farm Telemetry
Routes shared with drives - Where an IS loop runs beside motor cables or inverters, the braid holds transfer impedance at 250 Ω/km or less at 30 MHz.

03pharmaceutical-and-chemical-mixing-vessels-operator-in-cleanroom-clothing-beside-stainless-steel-mixing-tanks-with-sight-glasses

Pharmaceutical & Chemical Mixing Vessels
Outdoor runs between plant units - UV and weather resistance to ISO 4892-2 covers the open-air part of the route.

04grain-storage-and-silo-site-aerial-view-of-a-grain-facility-with-silos-sheds-and-trucks-on-the-yard

Grain Storage & Silo Dust Hazard Zones
Multi-core signal trunking - 2 to 25 cores in 0.75, 1.0 and 1.5 mm² let one cable carry a group of loops back to the marshalling cabinet.

 

Why Choose OLFLEX EB CY Series

 

Advantage

What it means on site

Full Compliance with IEC 60079-14 Hazardous Area Color Mandate

The sky-blue sheath at approximately RAL 5015 marks a type-i circuit along the whole route, so a maintenance crew can separate IS wiring from power wiring without opening a panel.

Certified Low Transfer Impedance 

High braid density holds transfer impedance at 250 Ω/km or less at 30 MHz, the figure that keeps switching noise off a 4–20 mA or thermocouple loop.

Outdoor Durability Certified to ISO 4892-2

UV and weather resistance is tested to ISO 4892-2, which is what puts open-air runs between plant units inside the range of this cable.

Low-Dielectric Core Construction with Documented Capacitance

Mutual capacitance of 160 nF/km core/core and 250 nF/km core/screen, with 0.52 mH/km inductance, are published figures, so a loop can be checked against the barrier's C_o and L_o before the order.

 

Frequently Asked Questions

 

Q: Why choose screened EB CY instead of unshielded OLFLEX EB?

A:  Where an IS loop shares a tray with drives, motor cables or contactors, the braid is what keeps coupled noise off the loop; transfer impedance is 250 Ω/km or less at 30 MHz. Where the route is segregated and the loop budget is tight, the unshielded EB carries 140 nF/km core/core.

Q: Why is the outer jacket of OLFLEX EB CY sky-blue?

A: The sheath is sky-blue, approximately RAL 5015 - the colour convention used to mark a type-i intrinsically safe circuit so that it is not mistaken for power wiring.

Q: Can OLFLEX EB CY be installed outdoors in direct sunlight?

A:Yes. The jacket is UV and weather resistant to ISO 4892-2, and outdoor use is one of the applications listed for this cable.

Q: How do I calculate the maximum allowable cable length for an IS loop with EB CY?

A: Determine the maximum external capacitance (C_o) and inductance (L_o) from the safety barrier certificate. Subtract the field instrument internal values (C_i, L_i). Divide the remaining capacitance budget by 160 nF/km (core-to-core) or 250 nF/km (core-to-screen, depending on grounding topology). Send us the C_o and L_o and we will check the loop against the published figures.

 

 

Hot Tags: olflex eb cy control cable, China olflex eb cy control cable suppliers

Comprehensive Mechanical & Electrical Ratings

 

Technical Parameter

Standard Reference & Certified Value

Conductor Type

Class 5 fine-wire bare copper conductor strands according to VDE 0295 / IEC 60228

Core Insulation

Special PVC compound LAPP P8/1; formulated for tight dimensional consistency and low dielectric loss

Core Identification

Black cores with continuous white Arabic numbering (VDE 0293-1); X series (no green-yellow earth)

Inner Wrapping

Plastic foil wrapping over stranded core bundle; protects cores during braid weaving and prevents inter-core adhesion

Screening / Braid

Tinned copper wire braided shield; high optical coverage for EMI rejection

Outer Sheath Material

Special PVC compound, flame-retardant to IEC 60332-1-2; sky-blue color similar to RAL 5015

UV & Weather Resistance

Certified UV and weathering resistance according to ISO 4892-2 (suitable for long-term outdoor exposure)

Rated Operating Voltage (U₀/U)

300/500 V (strictly for intrinsically safe circuit applications)

Dielectric Test Voltage

Core / Core: 3000 V AC | Core / Screen: 2000 V AC (spark tested)

Mutual Capacitance

Core / Core: approx. 160 nF/km | Core / Screen: approx. 250 nF/km (at 800 Hz)

Loop Inductance

Approx. 0.52 mH/km (at 800 Hz)

Transfer Impedance

Max. 250 Ω/km at 30 MHz

Minimum Bending Radius

Occasional flexing: 20 × cable outer diameter | Fixed installation: 6 × cable outer diameter

Operational Temperature Range

Occasional flexing: −5 °C to +70 °C | Fixed installation: −40 °C to +80 °C

 

Hazardous Area IS Circuit Design Parameters (IEC 60079-14 §16.2.2)

 

In an intrinsically safe circuit, the cable acts as an electrical energy reservoir. The distributed capacitance (C_c) and inductance (L_c) of the cable length must be subtracted from the maximum allowable external capacitance (C_o) and inductance (L_o) certified on the associated safety barrier or galvanic isolator.If the cable parameters exceed the barrier thresholds, the loop no longer meets its own safety case.

 

Certified Cable Electrical Parameter

Published Specification Value

Hazardous Area Loop Verification Impact

Engineering Design Calculation Rule

Mutual Capacitance (Core / Core)

Approx. 160 nF/km (0.160 nF/m)

Determines allowable transmission distance before exceeding safety barrier external capacitance limit (C_o).

Max Loop Length L_max = (C_o - C_i) / 160 nF/km. Compared to unshielded EB (140 nF/km), loop budget must factor the extra 20 nF/km.

Mutual Capacitance (Core / Screen)

Approx. 250 nF/km (0.250 nF/m)

Critical when instrument circuit is isolated from screen or when safety barrier specifies single-ended grounding.

Must be incorporated into loop safety verification calculations whenever screen is bonded to intrinsic safety earth busbar.

Loop Inductance (L_c)

Approx. 0.52 mH/km (0.52 µH/m)

Determines inductive energy storage under sudden current interruption or transmitter load disconnection.

Verify total cable inductance L_total = L_c × Length does not exceed barrier rating (L_o - L_i). The L/R ratio remains well below 25 µH/Ω.

Dielectric Insulation Test Voltage

Core/Core: 3000 V | Core/Screen: 2000 V

Guarantees dielectric integrity between adjacent IS circuits and from IS circuit to external structure earth.

Core/core 3000 V | Core/screen 2000 V - the cable is tested at both.

 

KABASI provides batch verification certificates showing precise mutual capacitance and loop inductance values for instrument loop certification dossiers.

 

IS Circuit Separation & Screen Grounding Rules (IEC 60079-14)

 

Proper field deployment of screened intrinsically safe cables requires strict adherence to installation boundaries. Violating grounding or separation rules invalidates the hazardous area explosion protection certification.

 

Installation Domain

Mandatory Code Requirement

Engineering Implementation Guideline

Segregation from Non-IS Cables

Minimum 50 mm clearance or earthed metal partition

In cable trays and marshaling racks, OLFLEX EB CY must be separated from power and 230 V lighting lines by a solid earthed barrier or 50 mm spatial air gap.

Screen Earthing Single-Point Rule

Screen must be connected to IS clean ground at ONE point only

To prevent circulating ground equalizing currents in hazardous areas, ground the tinned copper braid at the safety barrier busbar in the safe area; isolate shield at field instrument.

Identification across Cable Routes

Sky-blue color must remain visible throughout the plant

Where blue sheath enters non-IS raceways, maintain color identification; do not over-tape with black or grey heat shrink across transit spans.

Multi-Core Circuit Independence

Dielectric proof test ≥ 500 V between all isolated IS loops

OLFLEX EB CY is tested to 3000 V core-to-core, far exceeding the 500 V standard, allowing multiple independent IS loops in one 12-core or 25-core cable without crosstalk risk.

 

Metric to AWG Reference Notice

 

ÖLFLEX EB CY is manufactured exclusively to IEC 60228 metric conductor standards. The cross-reference table below provides approximate AWG sizes for engineering convenience. Always state the Lapp part number on purchasing contracts.

 

Metric Section (mm²)

Approximate AWG Equivalent

0.75

18

1.0

17

1.5

15

 

ÖLFLEX EB CY — Part Number Directory

 

Screened PVC control cable for type-i intrinsically safe circuits. X = all cores black with white consecutive numbers (no green-yellow ground). Complete catalogue listing from 0012640 to 0012666.

 

Part No.

Cores × mm²

AWG

Outer Diameter (mm)

Copper Index (kg/km)

Total Weight (kg/km)

0012640

2 X 0.75

18

6.2

43.0

56

0012641

3 X 0.75

18

6.5

52.0

70

0012642

4 X 0.75

18

7.0

61.0

95

0012643

5 X 0.75

18

7.7

72.0

108

0012644

7 X 0.75

18

8.3

89.0

168

0012645

12 X 0.75

18

10.9

138.0

216

0012646

18 X 0.75

18

12.7

211.0

315

0012647

25 X 0.75

18

14.8

280.0

435

0012650

2 X 1.0

17

6.5

51.0

84

0012651

3 X 1.0

17

6.8

62.0

110

0012652

5 X 1.0

17

8.1

88.0

156

Part No.

Cores × mm²

AWG

Outer Diameter (mm)

Copper Index (kg/km)

Total Weight (kg/km)

0012653

7 X 1.0

17

8.8

112.0

192

0012654

12 X 1.0

17

11.5

185.0

285

0012655

18 X 1.0

17

13.9

268.0

395

0012656

25 X 1.0

17

15.9

354.0

656

0012660

2 X 1.5

15

7.1

65.0

87

0012661

3 X 1.5

15

7.5

82.0

112

0012662

5 X 1.5

15

8.9

119.0

148

0012663

7 X 1.5

15

9.9

154.0

193

0012664

12 X 1.5

15

13.0

268.0

365

0012666

25 X 1.5

15

17.9

530.0

734

           

 

Send Inquiry