OLFLEX EB CY is the screened, sky-blue PVC control cable for type-i intrinsically safe circuits in hazardous industrial atmospheres. It is built to IEC 60079-14:2013 / EN 60079-14:2014 / VDE 0165-1:2014 clause 16.2.2, and the sky-blue sheath at approximately RAL 5015 keeps a type-i circuit distinguishable from power wiring along the whole route. A tinned copper braid sits over a plastic foil wrap, giving high braid density and a transfer impedance of 250 Ω/km or less at 30 MHz; the jacket is UV and weather resistant to ISO 4892-2. KABASI supplies bulk lengths or finished harnesses terminated to your schedule.
Select Your Variant
Screened vs. Unshielded: OLFLEX EB CY vs. OLFLEX EB
|
Engineering Evaluation Factor |
OLFLEX EB CY (Screened) |
OLFLEX EB (Unshielded) |
Selection Recommendation |
|
Shielding Architecture |
Tinned copper wire braided screen |
None (bare core lay-up under outer sheath) |
Specify EB CY where an IS loop shares a tray or raceway with drives or power cables. |
|
Mutual Capacitance (Core/Core) |
160 nF/km |
140 nF/km |
160 nF/km against 140 nF/km on the unshielded version; both figures enter the loop calculation against the barrier's C_o. |
|
Core-to-Screen Capacitance |
250 nF/km |
Not applicable (no screen) |
In high-noise petrochemical areas, the 250 nF/km, used in the loop calculation whenever the screen is bonded. |
|
Outer Diameter & Weight |
Slightly larger (e.g. 7 X 0.75 is 8.3 mm, 168 kg/km) |
Slimmer (e.g. 7 X 0.75 is 6.7 mm, 81 kg/km) |
Specify EB where space and barrier limits dominate; Specify EB where space and weight dominate; EB CY where the route carries drives or inverters. |
|
Outdoor & Weather Resistance |
Yes, UV resistant to ISO 4892-2 |
Yes, UV resistant to ISO 4892-2 |
Both versions are rated UV and weather resistant to ISO 4892-2. |
Typical Applications




Why Choose OLFLEX EB CY Series
|
Advantage |
What it means on site |
|
Full Compliance with IEC 60079-14 Hazardous Area Color Mandate |
The sky-blue sheath at approximately RAL 5015 marks a type-i circuit along the whole route, so a maintenance crew can separate IS wiring from power wiring without opening a panel. |
|
Certified Low Transfer Impedance |
High braid density holds transfer impedance at 250 Ω/km or less at 30 MHz, the figure that keeps switching noise off a 4–20 mA or thermocouple loop. |
|
Outdoor Durability Certified to ISO 4892-2 |
UV and weather resistance is tested to ISO 4892-2, which is what puts open-air runs between plant units inside the range of this cable. |
|
Low-Dielectric Core Construction with Documented Capacitance |
Mutual capacitance of 160 nF/km core/core and 250 nF/km core/screen, with 0.52 mH/km inductance, are published figures, so a loop can be checked against the barrier's C_o and L_o before the order. |
Frequently Asked Questions
Q: Why choose screened EB CY instead of unshielded OLFLEX EB?
A: Where an IS loop shares a tray with drives, motor cables or contactors, the braid is what keeps coupled noise off the loop; transfer impedance is 250 Ω/km or less at 30 MHz. Where the route is segregated and the loop budget is tight, the unshielded EB carries 140 nF/km core/core.
Q: Why is the outer jacket of OLFLEX EB CY sky-blue?
A: The sheath is sky-blue, approximately RAL 5015 - the colour convention used to mark a type-i intrinsically safe circuit so that it is not mistaken for power wiring.
Q: Can OLFLEX EB CY be installed outdoors in direct sunlight?
A:Yes. The jacket is UV and weather resistant to ISO 4892-2, and outdoor use is one of the applications listed for this cable.
Q: How do I calculate the maximum allowable cable length for an IS loop with EB CY?
A: Determine the maximum external capacitance (C_o) and inductance (L_o) from the safety barrier certificate. Subtract the field instrument internal values (C_i, L_i). Divide the remaining capacitance budget by 160 nF/km (core-to-core) or 250 nF/km (core-to-screen, depending on grounding topology). Send us the C_o and L_o and we will check the loop against the published figures.
Hot Tags: olflex eb cy control cable, China olflex eb cy control cable suppliers
Comprehensive Mechanical & Electrical Ratings
|
Technical Parameter |
Standard Reference & Certified Value |
|
Conductor Type |
Class 5 fine-wire bare copper conductor strands according to VDE 0295 / IEC 60228 |
|
Core Insulation |
Special PVC compound LAPP P8/1; formulated for tight dimensional consistency and low dielectric loss |
|
Core Identification |
Black cores with continuous white Arabic numbering (VDE 0293-1); X series (no green-yellow earth) |
|
Inner Wrapping |
Plastic foil wrapping over stranded core bundle; protects cores during braid weaving and prevents inter-core adhesion |
|
Screening / Braid |
Tinned copper wire braided shield; high optical coverage for EMI rejection |
|
Outer Sheath Material |
Special PVC compound, flame-retardant to IEC 60332-1-2; sky-blue color similar to RAL 5015 |
|
UV & Weather Resistance |
Certified UV and weathering resistance according to ISO 4892-2 (suitable for long-term outdoor exposure) |
|
Rated Operating Voltage (U₀/U) |
300/500 V (strictly for intrinsically safe circuit applications) |
|
Dielectric Test Voltage |
Core / Core: 3000 V AC | Core / Screen: 2000 V AC (spark tested) |
|
Mutual Capacitance |
Core / Core: approx. 160 nF/km | Core / Screen: approx. 250 nF/km (at 800 Hz) |
|
Loop Inductance |
Approx. 0.52 mH/km (at 800 Hz) |
|
Transfer Impedance |
Max. 250 Ω/km at 30 MHz |
|
Minimum Bending Radius |
Occasional flexing: 20 × cable outer diameter | Fixed installation: 6 × cable outer diameter |
|
Operational Temperature Range |
Occasional flexing: −5 °C to +70 °C | Fixed installation: −40 °C to +80 °C |
Hazardous Area IS Circuit Design Parameters (IEC 60079-14 §16.2.2)
In an intrinsically safe circuit, the cable acts as an electrical energy reservoir. The distributed capacitance (C_c) and inductance (L_c) of the cable length must be subtracted from the maximum allowable external capacitance (C_o) and inductance (L_o) certified on the associated safety barrier or galvanic isolator.If the cable parameters exceed the barrier thresholds, the loop no longer meets its own safety case.
|
Certified Cable Electrical Parameter |
Published Specification Value |
Hazardous Area Loop Verification Impact |
Engineering Design Calculation Rule |
|
Mutual Capacitance (Core / Core) |
Approx. 160 nF/km (0.160 nF/m) |
Determines allowable transmission distance before exceeding safety barrier external capacitance limit (C_o). |
Max Loop Length L_max = (C_o - C_i) / 160 nF/km. Compared to unshielded EB (140 nF/km), loop budget must factor the extra 20 nF/km. |
|
Mutual Capacitance (Core / Screen) |
Approx. 250 nF/km (0.250 nF/m) |
Critical when instrument circuit is isolated from screen or when safety barrier specifies single-ended grounding. |
Must be incorporated into loop safety verification calculations whenever screen is bonded to intrinsic safety earth busbar. |
|
Loop Inductance (L_c) |
Approx. 0.52 mH/km (0.52 µH/m) |
Determines inductive energy storage under sudden current interruption or transmitter load disconnection. |
Verify total cable inductance L_total = L_c × Length does not exceed barrier rating (L_o - L_i). The L/R ratio remains well below 25 µH/Ω. |
|
Dielectric Insulation Test Voltage |
Core/Core: 3000 V | Core/Screen: 2000 V |
Guarantees dielectric integrity between adjacent IS circuits and from IS circuit to external structure earth. |
Core/core 3000 V | Core/screen 2000 V - the cable is tested at both. |
KABASI provides batch verification certificates showing precise mutual capacitance and loop inductance values for instrument loop certification dossiers.
IS Circuit Separation & Screen Grounding Rules (IEC 60079-14)
Proper field deployment of screened intrinsically safe cables requires strict adherence to installation boundaries. Violating grounding or separation rules invalidates the hazardous area explosion protection certification.
|
Installation Domain |
Mandatory Code Requirement |
Engineering Implementation Guideline |
|
Segregation from Non-IS Cables |
Minimum 50 mm clearance or earthed metal partition |
In cable trays and marshaling racks, OLFLEX EB CY must be separated from power and 230 V lighting lines by a solid earthed barrier or 50 mm spatial air gap. |
|
Screen Earthing Single-Point Rule |
Screen must be connected to IS clean ground at ONE point only |
To prevent circulating ground equalizing currents in hazardous areas, ground the tinned copper braid at the safety barrier busbar in the safe area; isolate shield at field instrument. |
|
Identification across Cable Routes |
Sky-blue color must remain visible throughout the plant |
Where blue sheath enters non-IS raceways, maintain color identification; do not over-tape with black or grey heat shrink across transit spans. |
|
Multi-Core Circuit Independence |
Dielectric proof test ≥ 500 V between all isolated IS loops |
OLFLEX EB CY is tested to 3000 V core-to-core, far exceeding the 500 V standard, allowing multiple independent IS loops in one 12-core or 25-core cable without crosstalk risk. |
Metric to AWG Reference Notice
ÖLFLEX EB CY is manufactured exclusively to IEC 60228 metric conductor standards. The cross-reference table below provides approximate AWG sizes for engineering convenience. Always state the Lapp part number on purchasing contracts.
|
Metric Section (mm²) |
Approximate AWG Equivalent |
|
0.75 |
18 |
|
1.0 |
17 |
|
1.5 |
15 |
ÖLFLEX EB CY — Part Number Directory
Screened PVC control cable for type-i intrinsically safe circuits. X = all cores black with white consecutive numbers (no green-yellow ground). Complete catalogue listing from 0012640 to 0012666.
|
Part No. |
Cores × mm² |
AWG |
Outer Diameter (mm) |
Copper Index (kg/km) |
Total Weight (kg/km) |
|
0012640 |
2 X 0.75 |
18 |
6.2 |
43.0 |
56 |
|
0012641 |
3 X 0.75 |
18 |
6.5 |
52.0 |
70 |
|
0012642 |
4 X 0.75 |
18 |
7.0 |
61.0 |
95 |
|
0012643 |
5 X 0.75 |
18 |
7.7 |
72.0 |
108 |
|
0012644 |
7 X 0.75 |
18 |
8.3 |
89.0 |
168 |
|
0012645 |
12 X 0.75 |
18 |
10.9 |
138.0 |
216 |
|
0012646 |
18 X 0.75 |
18 |
12.7 |
211.0 |
315 |
|
0012647 |
25 X 0.75 |
18 |
14.8 |
280.0 |
435 |
|
0012650 |
2 X 1.0 |
17 |
6.5 |
51.0 |
84 |
|
0012651 |
3 X 1.0 |
17 |
6.8 |
62.0 |
110 |
|
0012652 |
5 X 1.0 |
17 |
8.1 |
88.0 |
156 |
|
Part No. |
Cores × mm² |
AWG |
Outer Diameter (mm) |
Copper Index (kg/km) |
Total Weight (kg/km) |
|
0012653 |
7 X 1.0 |
17 |
8.8 |
112.0 |
192 |
|
0012654 |
12 X 1.0 |
17 |
11.5 |
185.0 |
285 |
|
0012655 |
18 X 1.0 |
17 |
13.9 |
268.0 |
395 |
|
0012656 |
25 X 1.0 |
17 |
15.9 |
354.0 |
656 |
|
0012660 |
2 X 1.5 |
15 |
7.1 |
65.0 |
87 |
|
0012661 |
3 X 1.5 |
15 |
7.5 |
82.0 |
112 |
|
0012662 |
5 X 1.5 |
15 |
8.9 |
119.0 |
148 |
|
0012663 |
7 X 1.5 |
15 |
9.9 |
154.0 |
193 |
|
0012664 |
12 X 1.5 |
15 |
13.0 |
268.0 |
365 |
|
0012666 |
25 X 1.5 |
15 |
17.9 |
530.0 |
734 |