OLFLEX SERVO 2YSLCY-JB Motor Cable

OLFLEX SERVO 2YSLCY-JB Motor Cable
Details:
OLFLEX SERVO 2YSLCY-JB low-capacitance, double-screened motor cable: PE insulation, aluminium-laminated foil plus tinned copper braid, EN 61800-3, 0.6/1 kV, 4-core to 4 G 185 mm² and 3+3 symmetrical earth to 3 X 240 + 3 G 50 mm².

Standards & Compliance
EN 61800-3 | VDE 0207 / 0250 / 0295 | VDE 0293-308 | IEC 60332-1-2

Quick Specs
0.6/1 kV | 4000 V test | 1.5 – 185 mm² (4-core), 1.5 – 240 mm² (3+3) | −40 °C to +70 °C fixed | 15 × OD occasional flexing
Send Inquiry
Download
Overview
Technical Specifications
Part Numbers
Part Number & specification Verification | Availability & Lead Time Confirmation

Xiamen Kabasi Electric Co., Ltd. is one of the most reliable manufacturers and suppliers of olflex servo 2yslcy-jb motor cable in China. If you're going to buy bulk durable cables made in China, welcome to get pricelist from our factory. All customized cables are with high quality and competitive price.

 

Lead Paragraph

 

OLFLEX SERVO 2YSLCY-JB is the cable run between a frequency converter and its motor. PE core insulation gives it low capacitance, so the run between converter and drive can be longer. The screen is an aluminium-laminated plastic foil wrap under a tinned copper braid. The 4-core version comes with a transparent or a black PVC sheath, and the black one is suitable for outdoor use. The 3+3 symmetrical earth version reduces common-mode interference and bearing currents.

 

Select Your Variant

 

4-Core vs 3+3 Symmetrical Earth

Engineering Comparison Dimension

4-Conductor Version (SERVO 2YSLCY-JB)

3+3 Symmetrical Earth Version (SERVO 2YSLCYK-JB)

Earth One green-yellow core Three cores between the phases
Occasional flexing −5 to +70 °C −15 to +70 °C
Choose when Standard motor Bearing current is the issue

 

 

Typical Applications

 

01paper-mill-calender-stack-two-large-heated-rolls-in-yellow-housings-with-access-ladders-and-hydraulic-lines-on-the-machine-frame

Paper Mill Calendar Drive
Paper mill calendar drives run continuously off the converter, which is what the low-capacitance insulation is for on the run out to the machine.

02chemical-plant-cable-rack-outdoor-tray-run-carrying-multiple-black-sheathed-cables-above-a-rooftop-plant-deck-with-cooling-towers

Chemical Plant Cable Rack
Outdoors on a chemical plant the black sheath takes the run, and the earth is split into three for the large motor at the far end.

03rolling-mill-drive-cables-orange-and-grey-screened-servo-cables-with-metal-circular-connectors-coiled-for-delivery

Rolling Mill Drive Cabinet
A rolling mill reverses under load, so the double screen - foil under braid - is what keeps that switching inside the cable.

04container-crane-hoist-large-cable-reel-on-the-crane-trolley-with-gantry-cranes-and-stacked-containers-at-the-port-behind

Container Crane Hoist
On a crane the cabinet and the hoist motor sit far apart, and low-capacitance PE insulation is what makes that run practical.

 

Why Choose OLFLEX SERVO 2YSLCY-JB Series

 

Advantage

What it means on site

Low Capacitance Extends the Run Between Converter and Motor PE insulation keeps the capacitance of the cable low, which is what makes a longer run between the drive cabinet and the motor possible.
Double Screen for Power Drive Systems to EN 61800-3 Aluminium-laminated foil sits over the cores and a tinned copper braid over the foil. Together they are the screening arrangement a power drive system needs, to EN 61800-3.
Symmetrical 3+3 Earth Reduces Common-Mode and Bearing Currents The protective conductor is split into three and laid symmetrically between the phases, which is the arrangement used to reduce common-mode interference and the stray bearing currents that follow from it.
600/1000 V, 4000 V Test Voltage Rated 600/1000 V with a 4000 V test voltage core-to-core and core-to-screen, on 4-core cable up to 4 G 185 mm² and 3+3 up to 240 mm².

 

Frequently Asked Questions

 

Q: What is the cable built from?

A: Fine bare copper strands to VDE 0295 / IEC 60228 class 5, PE core insulation, concentric core lay-up, an aluminium-laminated foil wrap with a tinned copper braid over it, and a PVC sheath - transparent or black on the 4-core.

Q: Why is Polyethylene (PE) insulation superior to PVC for VFD motor cables?

A:PE is why the capacitance stays low, and low capacitance is what allows a longer run between the converter and the motor. That is the property being bought on a drive feeder.

Q: What is the specific engineering advantage of the 3+3 symmetrical earth configuration?

A:The 3+3 version splits the protective conductor into three and lays them symmetrically between the phases, which reduces common-mode interference and the stray bearing currents that come with it. Where bearing current is not the issue, the 4-core version covers 4 G 1.5 mm² to 4 G 185 mm².

Q: Why does OLFLEX SERVO 2YSLCY-JB incorporate two separate screening layers?

A: Aluminium-laminated foil sits over the cores and a tinned copper braid over the foil. The foil closes the gaps a braid leaves; the braid carries the screen current and gives the gland something to clamp. Both layers are what make this an EMC cable for power drive systems.

Q: Can the transparent outer sheath version be installed outdoors in open sunlight?

A: The black sheath is the one to specify outdoors. The transparent sheath is a 4-core option, chosen where the braid should stay visible under the jacket. For either, the stated application range is dry or damp interiors, so a run that leaves the building should be the black version.

 

 

Hot Tags: olflex servo 2yslcy-jb motor cable, China olflex servo 2yslcy-jb motor cable suppliers

Electrical, Mechanical & Symmetrical Construction Ratings

 

Technical Parameter

Standard Reference & Certified Value

Conductor Stranding

Fine-wire bare copper conductor strands according to VDE 0295 / IEC 60228 Class 5

Core Insulation Material

Low-capacitance polyethylene (PE)

Screening Structure

Double screen: aluminium-laminated plastic foil tape wrap plus tinned copper wire braid

Core Identification (4-core)

VDE 0293-308 color code (Brown, Black, Grey, Green-Yellow)

Core Identification (3+3 core)

3 phase cores (Brown, Black, Grey) + 3 protective earth conductors (Green-Yellow) symmetrically distributed

Outer Sheath Material

PVC; transparent or black. The black version is suitable for outdoor applications.

Nominal Operating Voltage (U₀/U)

600 / 1000 V AC (0.6 / 1 kV)

Dielectric Test Voltage

4000 V AC, core/core and core/screen

Minimum Bending Radius

Occasional flexing: 15 × cable outer diameter | Fixed installation: 4 × cable outer diameter

Temperature Range (4-core)

Occasional flexing: −5 °C to +70 °C | Fixed installation: −40 °C to +70 °C

Temperature Range (3+3 Version)

Occasional flexing: −15 °C to +70 °C (low-temperature flexibility) | Fixed installation: −40 °C to +70 °C

EMC System Compliance

EMC-optimised cable for power drive systems, to EN 61800-3

Flame Retardance

IEC 60332-1-2 single-cable vertical flame propagation test

 

 

Metric to AWG / kcmil Reference Notice

 

OLFLEX SERVO 2YSLCY-JB is manufactured to metric cross-sections with equivalent AWG / kcmil designations recognized for international engineering reference. Always specify the Lapp part number on purchasing documentation.

 

Metric Section (mm²)

Equivalent North American AWG / kcmil Designation

1.5

16

2.5

14

4.0

12

6.0

10

10.0

8

16.0

6

25.0

4

35.0

2

50.0

1

70.0

2/0

95.0

3/0

120.0

4/0

150.0

300 kcmil

185.0

350 kcmil

240.0

450 kcmil

 

OLFLEX SERVO 2YSLCY-JB

 

Low-capacitance double-screened motor supply cable (0.6/1 kV). Section A: 4-core Transparent jacket (0036425 to 0036438); Section B: 4-core UV-resistant Black jacket (1136450 to 1136463); Section C: Symmetrical 3+3 core Black jacket with low-temp flexibility (0036439 to 0036453). Integrated AWG column included.

 

Section A: 4-Core Version with Transparent PVC Outer Sheath

Part No.

Cores × mm²

AWG / kcmil

Outer Diameter (mm)

Copper Index (kg/km)

Total Weight (kg/km)

0036425

4 G 1.5

16 AWG

11.4

95.0

230

0036426

4 G 2.5

14 AWG

12.4

150.0

300

0036427

4 G 4.0

12 AWG

15.6

235.0

485

0036428

4 G 6.0

10 AWG

17.0

320.0

630

0036429

4 G 10.0

8 AWG

19.6

533.0

860

0036430

4 G 16.0

6 AWG

22.1

789.0

1290

0036431

4 G 25.0

4 AWG

26.3

1236.0

1860

Part No.

Cores × mm²

AWG / kcmil

Outer Diameter (mm)

Copper Index (kg/km)

Total Weight (kg/km)

0036432

4 G 35.0

2 AWG

29.5

1662.0

2610

0036433

4 G 50.0

1 AWG

35.8

2345.0

2950

0036434

4 G 70.0

2/0 AWG

40.3

3196.0

3950

0036435

4 G 95.0

3/0 AWG

46.5

4316.0

5300

0036436

4 G 120.0

4/0 AWG

53.2

5435.0

6600

0036437

4 G 150.0

300 kcmil

57.3

6394.0

7043

0036438

4 G 185.0

350 kcmil

62.3

7639.0

8384

 

Section B: 4-Core Version with Black UV-Resistant PVC Outer Sheath

Part No.

Cores × mm²

AWG / kcmil

Outer Diameter (mm)

Copper Index (kg/km)

Total Weight (kg/km)

1136450

4 G 1.5

16 AWG

11.4

95.0

230

1136451

4 G 2.5

14 AWG

12.4

150.0

300

1136452

4 G 4.0

12 AWG

15.6

235.0

485

1136453

4 G 6.0

10 AWG

17.0

320.0

630

1136454

4 G 10.0

8 AWG

19.6

533.0

860

1136455

4 G 16.0

6 AWG

22.1

789.0

1290

1136456

4 G 25.0

4 AWG

26.3

1236.0

1860

Part No.

Cores × mm²

AWG / kcmil

Outer Diameter (mm)

Copper Index (kg/km)

Total Weight (kg/km)

1136457

4 G 35.0

2 AWG

29.5

1662.0

2610

1136458

4 G 50.0

1 AWG

35.8

2345.0

2950

1136459

4 G 70.0

2/0 AWG

40.3

3196.0

3950

1136460

4 G 95.0

3/0 AWG

46.5

4316.0

5300

1136461

4 G 120.0

4/0 AWG

53.2

5435.0

6600

1136462

4 G 150.0

300 kcmil

57.3

6394.0

7043

1136463

4 G 185.0

350 kcmil

62.3

7639.0

8384

 

Section C: Symmetrical 3+3 Core Version (SERVO 2YSLCYK-JB) — Black Outer Sheath, Low-Temp Flexible

Part No.

Phase + Earth (mm²)

AWG / kcmil

Outer Diameter (mm)

Copper Index (kg/km)

Total Weight (kg/km)

0036439

3 X 1.5 + 3 G 0.25

16 + 24 AWG

11.4

88.0

140

0036440

3 X 2.5 + 3 G 0.5

14 + 20 AWG

12.2

144.0

220

0036441

3 X 4.0 + 3 G 0.75

12 + 18 AWG

14.4

224.0

323

0036442

3 X 6.0 + 3 G 1.0

10 + 17 AWG

15.7

276.0

420

0036443

3 X 10.0 + 3 G 1.5

8 + 16 AWG

18.0

491.0

615

0036444

3 X 16.0 + 3 G 2.5

6 + 14 AWG

20.2

723.0

819

0036445

3 X 25.0 + 3 G 4.0

4 + 12 AWG

23.8

1136.0

1325

0036446

3 X 35.0 + 3 G 6.0

2 + 10 AWG

26.9

1535.0

1718

Part No.

Phase + Earth (mm²)

AWG / kcmil

Outer Diameter (mm)

Copper Index (kg/km)

Total Weight (kg/km)

0036447

3 X 50.0 + 3 G 10.0

1 + 8 AWG

32.6

2156.0

2399

0036448

3 X 70.0 + 3 G 10.0

2/0 + 8 AWG

36.4

2871.0

3056

0036449

3 X 95.0 + 3 G 16.0

3/0 + 6 AWG

42.0

3953.0

4162

0036450

3 X 120.0 + 3 G 16.0

4/0 + 6 AWG

47.8

4836.0

5074

0036451

3 X 150.0 + 3 G 25.0

300 + 4 kcmil / AWG

51.6

5412.0

6128

0036479

3 X 185.0 + 3 G 35.0

350 + 2 kcmil / AWG

56.5

7041.0

7500

0036453

3 X 240.0 + 3 G 50.0

450 + 1 kcmil / AWG

65.1

8986.0

9770

           

 

Send Inquiry