OLFLEX CLASSIC 100 BK 0.6/1 KV Power Control Cable

OLFLEX CLASSIC 100 BK 0.6/1 KV Power Control Cable
Details:
OLFLEX CLASSIC 100 BK 0.6/1 kV black PVC power control cable to -30 C on occasional flexing, UV qualified to ISO 4892-2. Cut to length.

Standards & Compliance
IEC 60332-1-2 | ISO 4892-2 (UV) | EN 50396 (ozone) | VDE 0295 / IEC 60228 Class 5 | View standards

Quick Specs
0.6/1 kV | 4000 V test | −40 °C to +80 °C fixed / −30 °C to +70 °C flexing | UV-qualified black sheath (ISO 4892-2)
Send Inquiry
Download
Overview
Technical Specifications
Part Numbers
Part Number & specification Verification | Availability & Lead Time Confirmation

Xiamen Kabasi Electric Co., Ltd. is one of the most reliable manufacturers and suppliers of olflex classic 100 bk 0.6/1 kv power control cable in China. If you're going to buy bulk durable cables made in China, welcome to get pricelist from our factory. All customized cables are with high quality and competitive price.

 

Lead Paragraph

 

OLFLEX CLASSIC 100 BK 0.6/1 kV is the cold-climate member of the CLASSIC 100 family. It pairs the family's colour-coded Class 5 copper construction with a low-temperature PVC insulation and a black RAL 9005 sheath, extending occasional-flexing service down to −30 °C - a band standard PVC variants do not reach. That single material change makes the cable usable for outdoor cabinets, unheated plant rooms, cold stores and cold-region site wiring, where a standard PVC sheath stiffens and is difficult to dress. The black compound is also UV-qualified, with ageing assessed to ISO 4892-2 and ozone resistance tested under EN 50396.

 

What Separates the BK 0.6/1 kV Construction

 

Everything below the sheath follows the same discipline as the rest of the family - Class 5 fine-wire bare copper, PVC insulation, colour-coded cores and the G / X earth-core option. What changes is the insulation compound, the sheath compound and the voltage grade, and those three changes are what the ordering decision turns on.

 

Property

CLASSIC 100 BK 0.6/1 kV

Standard CLASSIC 100 (300/500 V, 450/750 V)

Nominal voltage U₀/U

0.6/1 kV

300/500 V or 450/750 V

Core insulation

Low-temperature PVC

PVC

Outer sheath

Low-temperature PVC, black RAL 9005

PVC, grey RAL 7001 or black RAL 9005

Temperature - occasional flexing

−30 °C to +70 °C

−5 °C to +70 °C

Temperature - fixed installation

−40 °C to +80 °C

−40 °C to +80 °C

Outdoor UV qualification

ISO 4892-2 (UV) / EN 50396 (ozone)

Not specified

 

One consequence is worth stating plainly: the low-temperature compound is thicker than the standard PVC used on the 300/500 V grade, so the BK 0.6/1 kV cable is larger in outer diameter for the same conductor area. A four-core 0.5 mm² building is 7.6 mm here against 5.7 mm on the grey 300/500 V version. Tray fill and duct sizing have to be planned on this cable's dimensions, not on the dimensions of the control-grade version.

 

Typical Applications

 

01outdoor-distribution-cabinet-on-a-wooden-pole-beside-a-snowy-road-built-for-cold-region-service

Outdoor distribution cabinets and pole-mounted boards in cold regions.
Where the cable has to stay serviceable through a winter that a standard PVC sheath would not tolerate.

02unheated-plant-room-a-row-of-grey-motor-control-and-distribution-cabinets-in-a-refrigerated-facility

Unheated plant rooms, cold stores and refrigerated facilities.
Power control circuits in spaces that are deliberately held below normal ambient temperature.

03rooftop-cable-tray-run-in-direct-sunlight-black-uv-qualified-cables-laid-along-trays-above-the-building

Rooftop and outdoor cable-tray runs in direct sunlight.
The UV-qualified black compound is the reason this variant is chosen over the grey control grade for permanent outdoor routes.

04remote-equipment-cabinet-and-site-power-control-pad-mounted-enclosure-with-pole-mounted-cable-terminations-in-open-terrain

Remote equipment cabinets and site power control.
Combined exposure to low ambient temperature and daylight on one cable, at the 0.6/1 kV grade those circuits require.

 

Why Specify CLASSIC 100 BK 0.6/1 kV

 

A 0.6/1 kV grade for plant-level distribution.

The voltage class suits distribution and power control circuits where the 300/500 V control grade would be out of scope.

01

Occasional flexing down to −30 °C.

The low-temperature compound extends the working window 25 °C beyond the standard PVC variants, which stop at −5 °C for occasional flexing.

02

A sheath that is qualified for daylight.

UV ageing assessed to ISO 4892-2 and ozone resistance tested to EN 50396 on the black compound, so the cable is not a compromise when it has to live outside.

03

The family's core identification and earth-core options.

Colour-coded cores to VDE 0293-308 and the printed colour code, with G and X versions, so a cold-climate installation is wired the same way as any other panel on the site.

04

 

Frequently Asked Questions

 

Q: Why is the occasional-flexing limit −30 °C on this variant?

A: Because the core insulation and the outer sheath both use a low-temperature PVC compound instead of the standard PVC used on the other variants. The compound keeps enough flexibility at low temperature for the cable to be dressed into a terminal compartment, which the standard PVC variants cannot do below −5 °C.

Q: What is the difference between the fixed and the flexing temperature limits?

A: Two limits apply and the operating condition decides which: a static run uses −40 °C to +80 °C, and any handling or dressing of the cable uses −30 °C to +70 °C. The stricter limit governs whenever the cable is moved.

Q: Can this cable be installed outdoors in direct sunlight?

A: Yes. The black compound is qualified for outdoor exposure, with UV ageing assessed to ISO 4892-2 and the material tested for ozone resistance under EN 50396. Support the cable along the run rather than letting it carry span load, and confirm the route radius against the 4 × outer diameter fixed bend radius.

Q: Is the 0.6/1 kV grade a substitute for the 450/750 V variant?

A: No - they serve different circuits. The 450/750 V grade reaches 185 mm² and is intended for power and motor supply, while this variant tops out at 35 mm² and is intended for power control circuits that have to operate in cold or outdoor conditions. Where the constraint is conductor area, the 450/750 V grade is the answer; where it is temperature and weathering, this variant is.

Q: Which core identification applies?

A: Up to five cores the cable uses solid core colours to VDE 0293-308, with green-yellow reserved for the protective earth. From six cores upward it uses the printed colour code. G versions include the earth core; X versions do not.

 

 

Hot Tags: olflex classic 100 bk 0.6/1 kv power control cable, China olflex classic 100 bk 0.6/1 kv power control cable suppliers

Electrical and Thermal Ratings

 

Parameter

Rating

Nominal voltage U₀/U

0.6/1 kV

Factory dielectric test

4000 V, applied to every production length

Temperature - fixed installation

−40 °C to +80 °C

Temperature - occasional flexing

−30 °C to +70 °C

Flame retardancy

IEC 60332-1-2, single-wire vertical flame test

Weathering and UV

UV ageing assessed to ISO 4892-2; ozone resistance tested to EN 50396

 

Construction and Core Identification

 

Layer / Property

Specification

Conductor

Class 5 fine-wire bare copper, VDE 0295 / IEC 60228 Class 5

Insulation

Low-temperature PVC, colour-coded

Identification - up to 5 cores

Solid core colours to VDE 0293-308

Identification - 6 cores and above

Colour code applied over the printed scheme

Protective conductor

G = green-yellow earth core included; X = no earth core

Outer sheath

Low-temperature PVC, black RAL 9005

 

The Sub-Zero Installation Envelope

 

PVC does not fail abruptly at low temperature; it loses impact resistance and flexibility as it approaches the glass transition, and a sheath that would shrug off a knock at +20 °C can crack at −30 °C. The two published limits on this cable describe different duties, and confusing them is the usual cause of a winter installation failure.

 

Operation

Limit on BK 0.6/1 kV

What the Limit Protects

Fixed installation

−40 °C to +80 °C

Static runs, tray work and ducted cable - the sheath is not being deformed

Occasional flexing

−30 °C to +70 °C

Dressing into a terminal compartment, minor re-routing and panel work

Standard PVC variants, for comparison

−5 °C to +70 °C on occasional flexing

Shows how far the low-temperature compound extends the working window

 

In practice the −30 °C figure is a handling limitation as much as a service limitation. Cold cable that has been stored outdoors should be allowed to come up in temperature before it is uncoiled, since a coil pulled open while the compound is stiff puts the bend load into the conductors rather than distributing it along the sheath. Keep the drum under cover before the pull, avoid dropping or impact-loading the coil, and respect the 4 × outer diameter fixed bend radius - at this construction the radius is larger than the control-grade equivalent because the outer diameter is larger.

 

Four-Core Size

Outer Diameter

Fixed Radius (4 × OD)

4G0.5

7.6 mm

≈ 30 mm

4G1.5

10.8 mm

≈ 43 mm

4G2.5

12.2 mm

≈ 49 mm

4G6

15.1 mm

≈ 60 mm

4G16

21.3 mm

≈ 85 mm

4G35

29.1 mm

≈ 116 mm

 

Outdoor Weathering and UV Exposure

 

A black sheath is not automatically a weather-resistant sheath, which is why this variant is qualified against two environmental-ageing references rather than one. UV ageing is assessed to ISO 4892-2, the laboratory xenon-arc exposure method used to predict the effect of sunlight and moisture on plastics, and the material is tested for ozone resistance under EN 50396. 

 

Exposure Factor

Design Response

Direct sunlight on unshaded tray

The black compound is the UV-qualified construction in the family; the grey and standard-PVC variants carry no UV qualification

Combined cold and UV exposure

The low-temperature insulation and the UV-qualified sheath address both stressors on one cable rather than through two separate products

Long-term outdoor service

Support the cable along the full run so the sheath is not carrying span load, and keep the fixed bend radius in mind, since it is larger than on the control-grade version

Coastal and humid environments

Specify the installation details with the enquiry so the sheath finish and any additional protection can be confirmed

 

Reading the Part Number Tables

 

AWG figures are nearest-area equivalents converted from the metric cross-section and are not interchangeable with AWG-specified products. On this page the equivalent column runs from 20 AWG at 0.5 mm² through 13 AWG at 2.5 mm² and 9 AWG at 6 mm², ending at 2 AWG at 35 mm². Confirm any AWG requirement against the metric size before ordering. In the designation, G means the green-yellow earth core is fitted and X means it is not.

 

CLASSIC 100 BK 0.6/1 kV — Part Number Table

 

Part No.

Cores × mm²

AWG

OD (mm)

Cu (kg/km)

Weight (kg/km)

1120450

2×0.5

20

6.4

9.6

56

1120451

3G0.5

20

6.8

14.4

68

1120452

4G0.5

20

7.6

19.2

100

1120453

5G0.5

20

8.2

24.0

117

1120456

2×1

17

8.6

19.2

98

1120457

3G1

17

9.0

29.0

112

1120458

4G1

17

9.6

38.0

131

1120459

5G1

17

10.4

48.0

152

1120462

2×1.5

15

9.6

29.0

123

1120463

3G1.5

15

10.1

43.0

144

Part No.

Cores × mm²

AWG

OD (mm)

Cu (kg/km)

Weight (kg/km)

1120464

4G1.5

15

10.8

58.0

170

1120468

2×2.5

13

10.8

48.0

147

1120469

3G2.5

13

11.3

72.0

182

1120470

4G2.5

13

12.2

96.0

225

1120474

4G4

11

13.8

154.0

324

1120475

4G6

9

15.1

230.0

442

1120476

4G10

7

18.7

384.0

707

1120477

4G16

5

21.3

614.0

1,100

1120478

4G25

3

26.2

960.0

1,600

1120479

4G35

2

29.1

1,344.0

2,400

 

Send Inquiry