The rated voltage for shielded control cables is typically 450/750V. According to relevant specifications, a rated voltage of 450/750V should be selected for control cables installed in high-voltage distribution equipment rated at 220kV and above; this rating is also recommended for control cables in other applications, although a lower rated voltage may be used when external electrical interference is minimal.
Common nominal cross-sectional areas for cable conductors range from 0.5 mm² to 6 mm², including sizes such as 0.5 mm², 0.75 mm², 1.0 mm², 1.5 mm², and 2.5 mm². For specific types, such as computer cables, the number of conductor pairs can range from 1 to 40.
The maximum permissible long-term operating temperature for cable conductors varies depending on the model and materials used. For instance, the long-term operating temperature for cables with PVC insulation typically does not exceed 70°C, whereas cables with cross-linked polyethylene (XLPE) insulation can operate at temperatures up to 90°C. The ambient temperature during cable installation should be no lower than 0°C.
The minimum permissible bending radius during installation is determined by the cable structure: for unarmored cables, it should be at least 6 times the outer diameter; for armored cables or those with copper tape shielding, it should be at least 12 times the outer diameter; and for flexible cables with shielding, it should be at least 6 times the outer diameter.
In addition to standard models, cables with special properties-such as flame-retardant, intrinsically safe, or high-temperature resistant types-can be manufactured to meet user requirements. The production and testing of shielded control cables must comply with relevant national standards, such as GB/T 9330-2020 "Plastic Insulated Control Cables."