Grounding a Spare Core in the Control Cable
Practical experience shows that grounding a spare core within a control cable can reduce the amplitude of interference voltage to 25%–50%. This method is simple to implement and adds very little to the cable's cost.
Circuits where electrical interference could lead to serious consequences should not share the same control cable; these include: low-voltage signal control circuits and high-voltage signal control circuits;
Loops involving both low-level and high-level signals;
Low-voltage control circuits for the individual phases of AC circuit breakers operated on a per-phase basis should not share the same control cable. However, if the go-and-return conductors of a low-voltage circuit are placed in separate control cables, a loop configuration may form during installation; electromagnetic coupling could then induce a potential that might affect the low-current circuit. Since low-level signal parameters are highly susceptible to interference, it is recommended to use the same control cable for both the go and return conductors.
Metal Shielding and Shield Grounding
Metal shielding is a crucial measure for mitigating and preventing electrical interference; options include overall shielding, individual core shielding, and double-layer overall shielding. The choice of metal shielding type for control cables should be based on the intensity of potential electrical interference, employing comprehensive anti-interference measures to meet requirements for reducing interference and overvoltage. Higher requirements for interference suppression entail higher investment costs; for instance, using steel-tape armor or steel-wire braiding for overall shielding increases the cable price by approximately 10% to 20%.