UNITRONIC LiHCH Data Cable

UNITRONIC LiHCH Data Cable
Details:
UNITRONIC LiHCH screened halogen-free (LSZH) data cable: tinned copper wire braid for high-frequency EMC immunity, DIN 47100 color code, VDE 0812 compliant, IEC 60754-1/2 non-corrosive, for public buildings and industrial telemetry.

Standards & Compliance
Based on VDE 0812 | DIN 47100 Core Colors | High-Coverage Tinned Copper Braid | IEC 60754-2 | IEC 61034-2 | IEC 60332-1-2 Flame Retardant

Quick Specs
250 V (Halogen-Free) peak | 1200 V AC test | 0.14 – 1.5 mm² (2–25 cores) | −30 °C to +80 °C fixed | DIN 47100 cores, overall tinned copper braid screen, concentric lay
Send Inquiry
Download
Overview
Technical Specifications
Part Numbers
Part Number & specification Verification | Availability & Lead Time Confirmation

Xiamen Kabasi Electric Co., Ltd. is one of the most reliable manufacturers and suppliers of unitronic lihch data cable in China. If you're going to buy bulk durable cables made in China, welcome to get pricelist from our factory. All customized cables are with high quality and competitive price.

 

Lead Paragraph

 

UNITRONIC LiHCH is a screened halogen-free data cable for buildings where sensitive signals share space with power. A high-coverage tinned copper braid acts as a Faraday cage, diverting inverter hash and inductive switching spikes to ground, while concentric-laid cores with low mutual capacitance keep 4–20 mA transmitter loops, RTD inputs and encoder channels clean. The LSZH polyolefin insulation and jacket satisfy IEC 60754-1/2 for acid-gas-free combustion and IEC 61034-2 for low smoke density, so hospitals, data centres and airport terminals get telemetry integrity and fire safety from one cable. Forty configurations run from 2-core 0.14 mm² to 3-core 1.5 mm². KABASI supplies precision-cut reels and pre-tested assemblies with 360° EMC terminations.

 

Select Your Variant

 

Screened Data Cable Comparison: LiHCH (Concentric Layer) vs. LiHCH (TP) (Twisted Pair)

Engineering Comparison Dimension

UNITRONIC LiHCH (Concentric Layered)

UNITRONIC LiHCH (TP) (Twisted Pair)

System Engineering Decision Matrix

Internal Conductor Geometry

Cores stranded in concentric circular layers

Cores paired and twisted (TP) with calculated lay lengths

Specify LiHCH for discrete I/O, analogue 4–20 mA and display runs; specify LiHCH (TP) where adjacent channels carry dissimilar signal levels.

Internal Crosstalk Attenuation

Moderate channel-to-channel capacitive coupling

Near-end crosstalk (NEXT) canceled by balanced magnetic field decoupling

Choose LiHCH (TP) where adjacent core channels carry disparate signal amplitudes or asynchronous digital pulses.

Cable Outer Diameter & Space

Noticeably more compact across identical core counts (e.g. 4-core 0.25 is 5.2 mm)

Slightly larger profile (e.g. 2 x 2 x 0.25 is 6.5 mm)

LiHCH is ideal where multi-channel cable trays are space-constrained and cross-pair decoupling is not required.

Stripping & Termination Speed

Rapid stripping; single outer sheath and unified braid cut

Requires pair separation and individual pair unwinding

LiHCH delivers significantly faster wiring throughput in standard PLC marshaling cabinets.

 

Typical Applications

 

01low-voltage-switchgear-room-a-row-of-floor-standing-distribution-cabinets-along-a-service-corridor-with-cable-tray-and-lighting-trunking-overhead

Public Buildings - Hospital Building Services
A hospital services cabinet sits in a building where a fire has to stay survivable long enough for people to walk out, so what the sheath releases matters as much as what the cable carries: no halogen, low smoke density to IEC 61034-2.

02ceiling-void-above-a-public-concourse-bundled-cables-and-conduit-runs-dropping-between-the-steel-ribs-and-suspended-lighting

Transport Systems - Airport Baggage Hall
A baggage hall ceiling void is shared with conveyor drives and lighting circuits, and the tinned copper braid is what keeps that switching noise off the signal runs to the sortation controllers.

03machine-positioning-axis-aluminium-profile-frame-with-a-pneumatic-cylinder-position-sensors-and-a-small-breaker-block-beside-the-control-cabinet

Factory Floor - Machine Tool Measuring Circuits
An 8 × 0.14 mm² run to a linear scale carries a small signal through a machine full of drives, which is why the insulation is polyolefin and mutual capacitance stays at about 80 nF/km.

04control-cabinet-interior-breaker-rows-relay-modules-an-orange-contactor-and-dense-terminal-strips-wired-with-blue-and-grey-cores

Office Equipment - In-Cabinet Wiring
Instrument and office-equipment panels are the case this family exists for - screened, halogen-free, small-section - with 4 × 0.75 mm² at 7.2 mm OD bending to 10 × OD when the cabinet is reworked.

 

Why Choose UNITRONIC LiHCH Series

 

Advantage

What it means on site

Dense Tinned Copper Braid Guarantees High-Frequency EMC Protection

Suppresses high-frequency electrical hash and inverter noise, preventing signal corruption in dense factory floors and medical hubs.

Zero-Halogen Fire Safety - IEC 60754-1/-2 and IEC 61034-2

Releases no corrosive hydrogen chloride fumes (IEC 60754-1/2) and preserves optical visibility (IEC 61034-2), ensuring uncompromised life safety across public transportation hubs.

Broad 40-Item Directory Spans from 0.14 mm² to 1.50 mm²

Offers unmatched channel scalability from miniature 0.14 mm² transducer wires up to robust 1.5 mm² control lines, allowing facility-wide specification under one standardized family.

Low-Capacitance Polyolefin Insulation Preserves Pulse Sharpness

Mutual capacitance of 80 nF/km (core/core) prevents pulse front-edge degradation, ensuring reliable analog readings and crisp digital telemetry over extended cable runs.

 

Electromagnetic Compatibility (EMC): What the Braid Does and How to Terminate It

 

Electromagnetic interference in industrial and medical facilities predominantly originates from switching transistors in frequency inverters, heavy relay contact arcing, and radio transmitters. UNITRONIC LiHCH utilizes a heavy tinned copper braid shield to enforce signal immunity across a broad frequency spectrum:

 

EMC Shielding Criterion

Physical Mechanism in UNITRONIC LiHCH

Performance Threshold & Value

Operational Benefit in Real-World Installations

Transfer Impedance 

Current redistribution across interwoven copper wire strands

≤ 250 Ω/km at 30 MHz high-frequency test

Prevents high-frequency common-mode noise voltages from penetrating internal signal cores.

Electrostatic Noise Divergence

Continuous conductive boundary around stranded core lay-up

Capacitive coupling to shield: ~120 nF/km

Diverts stray capacitive displacement currents directly to enclosure ground bus before reaching sensitive inputs.

Braid Optical Coverage

Tightly woven fine tinned copper wire weave

Nominal optical coverage ≥ 80% to 85%

Eliminates high-frequency aperture leakage, outperforming simple spiral wraps or thin unbacked foil.

360° Termination Interface

Compatible with EMC-compliant brass cable glands

Low-resistance 360-degree bonding ring contact

Eliminates inductive "pigtail" drain wire resonances that otherwise destroy high-frequency shield efficacy.

 

Deploying UNITRONIC LiHCH guarantees that sensitive analog instrumentation operates without erratic drift or false threshold alarms even when installed in close proximity to commercial building elevators and chiller drives.

 

Frequently Asked Questions

 

Q: What is the structural difference between "LiHH" and "LiHCH"?

A: The letter "C" in "LiHCH" indicates a copper braided screen ("Cu-Geflecht" in German cable nomenclature). While LiHH consists of bare unshielded insulated cores beneath a halogen-free jacket, LiHCH adds an overall tinned copper wire braided screen beneath the outer sheath, providing superior electromagnetic shielding against external electrical noise.

Q: Why is tinned copper wire preferred over bare copper for the braided screen?

A: Tinned copper wire offers substantially higher resistance to atmospheric oxidation, moisture corrosion, and corrosive industrial atmospheres. Tin plating also enhances solderability when attaching shield ground leads and ensures long-term low contact resistance within 360° EMC cable gland clamping cones.

Q: How should the shield of UNITRONIC LiHCH be grounded in an analog 4–20 mA loop?

A: For low-frequency analog sensor loops (4–20 mA or 0–10 V), the shield should generally be connected to ground at one end only (typically at the PLC or DCS cabinet instrument earth bus). This prevents power-frequency ground loop currents from circulating through the shield and inducing 50 Hz/60 Hz hum onto sensitive analog readings.

Q: Can UNITRONIC LiHCH be installed in continuous cable drag chains?

A: No. UNITRONIC LiHCH is engineered for fixed installations or occasional non-continuous flexing (minimum bending radius 10 × OD). For continuous high-speed movement inside automated drag chains, specify UNITRONIC FD CP (TP) plus or ÖLFLEX CHAIN families designed specifically for millions of flexural cycles.

Q: Does the shield add significant weight and stiffness compared to unshielded LiHH?

A: Yes. The tinned copper braid increases both cable weight and mechanical rigidity. For example, 4-core 0.25 mm² unshielded LiHH weighs 28 kg/km with a 4.5 mm diameter, whereas screened LiHCH weighs 35 kg/km with a 5.2 mm diameter. However, this modest profile increase delivers complete high-frequency noise immunity.

 

 

Hot Tags: unitronic lihch data cable, China unitronic lihch data cable suppliers

Electrical, Mechanical & Screen Construction Ratings

 

Technical Parameter

Standard Reference & Certified Value

Conductor Stranding

Fine multi-strand bare copper; 0.34 mm² is 7 strands, based on VDE 0812

Core Insulation

Special halogen-free polyolefin compound (reduced mutual capacitance)

Screening Structure

Tinned copper wire braided screen

Core Identification

DIN 47100 standard color code without color repetition

Core Lay-Up

Cores laid up under an overall braid

Outer Sheath Material

Special halogen-free flame-retardant compound (LSZH), pebble grey (similar to RAL 7032)

Peak Operating Voltage

250 V (for low-voltage data, signal and instrumentation circuits)

Dielectric Test Voltage

1200 V 

Mutual Capacitance (Core/Core)

Approx. 80 nF/km 

Mutual Capacitance (Core/Screen)

Approx. 120 nF/km 

Inductance

Approx. 0.65 mH/km

Minimum Bending Radius

Occasional flexing: 10 × outer diameter | Fixed installation: 6 × outer diameter

Temperature Range (Flexing)

−5 °C to +70 °C

Temperature Range (Fixed)

−30 °C to +80 °C

Halogen Acid Gas Emission

IEC 60754-1 (< 5 mg/g HCl, zero halogens)

Corrosiveness of Combustion Gases

IEC 60754-2 (pH ≥ 4.3; electrical conductivity ≤ 10 µS/mm)

Smoke Density & Visibility

IEC 61034-2 (optical light transmittance ≥ 60%)

Toxicity of Combustion Fumes

EN 50305 low toxicity index compliance

Flame Retardance

IEC 60332-1-2 single-cable vertical flame propagation test

 

Screen Earthing & 360° Shield Termination Rules for Noise-Free Signal Telemetry

 

A high-quality copper braid shield only delivers its theoretical attenuation when correctly bonded to the enclosure ground at termination points:

 

Earthing Practice

Correct Engineering Execution

Improper Shortcut to Avoid

Technical Consequence on Signal Integrity

360° Circumferential Clamping

Use EMC brass cable glands with conductive spring contact rings that clamp the braid circumferentially around its entire 360° perimeter

Do not twist the braid into a thin wire strand ("pigtail") and screw it under a generic ground lug

Pigtails introduce high parasitic inductance (L ≈ 1 nH/mm); at 30 MHz, a 50 mm pigtail adds ~9.4 Ω impedance, rendering the shield useless against HF noise.

Single-Point vs. Dual-Point Earthing

For low-frequency analog circuits (0–10V, 4–20mA), ground the braid at the controller end only; for high-frequency digital telemetry, ground at both ends with equipotential bonding

Never ground both ends when significant ground potential differences (> 1 V) exist between field sensors and controllers

Ground potential differentials cause large power-frequency loop currents to flow through the braid, injecting 50/60 Hz hum directly into analog inputs.

Continuity Across Enclosure Bulkheads

Maintain shield continuity through partition walls using dedicated feedthrough EMC glands or feedthrough connectors

Never break the shield and allow bare cores to bridge bulkheads over open air

Unshielded gaps allow radiated motor drive emissions to bypass the cable screen entirely.

Shield Separation from Low-Z Ground Bus

Connect the enclosure ground bus bar directly to clean instrument earth (PE) with impedance < 1.0 Ω

Do not share signal shield ground bars with high-power inverter motor grounding studs

Prevents heavy motor fault currents from back-feeding into sensitive instrument cable braids.

 

Metric to AWG Reference Notice

 

UNITRONIC LiHCH is manufactured to metric cross-sections with equivalent AWG ratings recognized for international engineering reference.

 

Metric Section (mm²)

Equivalent North American AWG Designation

0.14

26

0.25

24

0.34

22

0.5

20

0.75

18

1.0

17

1.5

16

 

UNITRONIC LiHCH — Part Number Directory

 

Halogen-free screened flexible data cable with DIN 47100 color code and overall copper braid. Selected catalogue listing from 0037302 to 0037903 with integrated AWG equivalents.

 

Part No.

Cores × mm²

Equivalent AWG

Outer Diameter (mm)

Copper Index (kg/km)

Total Weight (kg/km)

0037302

2 x 0.14

26 AWG

4.1

12.0

22

0037308

8 x 0.14

26 AWG

6.0

26.0

41

0037325

25 x 0.14

26 AWG

8.7

63.0

149

0037402

2 x 0.25

24 AWG

4.7

15.0

25

0037407

7 x 0.25

24 AWG

6.2

32.0

52

0037425

25 x 0.25

24 AWG

10.9

114.0

172

0037502

2 x 0.34

22 AWG

5.1

17.0

30

0037508

8 x 0.34

22 AWG

8.0

45.0

84

0037525

25 x 0.34

22 AWG

12.1

144.0

259

0037602

2 x 0.5

20 AWG

5.8

29.0

38

Part No.

Cores × mm²

Equivalent AWG

Outer Diameter (mm)

Copper Index (kg/km)

Total Weight (kg/km)

0037605

5 x 0.5

20 AWG

7.2

50.0

76

0037608

8 x 0.5

20 AWG

8.9

75.0

135

0037618

18 x 0.5

20 AWG

11.7

134.0

239

0037702

2 x 0.75

18 AWG

6.2

35.0

45

0037704

4 x 0.75

18 AWG

7.2

56.0

80

0037802

2 x 1.0

17 AWG

6.5

43.0

72

0037804

4 x 1.0

17 AWG

7.5

68.0

109

0037807

7 x 1.0

17 AWG

8.8

118.0

171

0037902

2 x 1.5

16 AWG

7.3

58.0

90

0037903

3 x 1.5

16 AWG

7.7

74.0

115

 

Send Inquiry