HELUKABEL H05V-K Single Core Hook-Up Wire

HELUKABEL H05V-K Single Core Hook-Up Wire
Details:
H05V-K PVC single-core panel wire to DIN EN 50525-2-31 and IEC 60227-3 — class 5 bare copper, 0.5 to 1.0 mm², seventeen colours, 300 / 500 V.

Standards & Compliance
DIN VDE 0285-525-2-31 | DIN VDE 0295 cl. 5 | IEC 60332-1 | Low Voltage Directive 2014/35/EU

Quick Specs
300 / 500 V U0/U | Class 5 fine bare copper | 5 to +70 °C flexing · −30 to +80 °C fixed | 2000 V test | 0.5 – 1.0 mm² harmonised
Send Inquiry
Download
Overview
Technical Specifications
Part Numbers
Part Number & specification Verification | Availability & Lead Time Confirmation

Xiamen Kabasi Electric Co., Ltd. is one of the most reliable manufacturers and suppliers of helukabel h05v-k single core hook-up wire in China. If you're going to buy bulk durable cables made in China, welcome to get pricelist from our factory. All customized cables are with high quality and competitive price.

 

Positioning of the Harmonised Panel Range

 

H05V-K is a PVC single-core wire built to DIN VDE 0285-525-2-31 / DIN EN 50525-2-31 and IEC 60227-3, with a bare copper conductor fine-stranded to DIN VDE 0295 class 5 (BS 6360 class 5, IEC 60228 class 5). Insulation is PVC compound type TI1 to DIN VDE 0207-363-3 / DIN EN 50363-3 and IEC 60227-3.

 

Three cross-sections cover 0.5, 0.75 and 1.0 mm² at 300 / 500 V U0/U against a 2000 V test. Insulation resistance is a minimum of 10 MOhm x km, the fixed bending radius is 4 x core Ø, and the compound withstands radiation up to 80 x 10⁶ cJ/kg (80 Mrad). It is self-extinguishing and flame-retardant to DIN VDE 0482-332-1-2, DIN EN 60332-1-2 and IEC 60332-1, and the materials used are cadmium-free, free from silicone and free from substances that impair the wetting properties of lacquers.

 

Seventeen colour options are supplied in three packaging forms - a 100 m cardboard box, a plastic spool and a cardboard drum, the last two in several capacities. The range conforms to Low Voltage Directive 2014/35/EU.

 

H05V-K is specified for installation inside equipment, as a protective lead for luminaires, and in dry rooms, production halls, switchgear and distribution equipment, in conduit, and under or on plaster. It is not an outdoor wire and it is not a power distribution cable.

 

Cross-Section

 

The three sizes differ only in conductor, diameter and copper weight; the insulation, the voltage class and the construction are common.

 

Cross-section

Outer diameter

Copper weight

Nominal voltage

Test voltage

0.50 m㎡

2.1 - 2.5 mm

4.8 kg/km

300 / 500 V

2000 V

0.75 m㎡

2.2 - 2.7 mm

7.2 kg/km

300 / 500 V

2000 V

1.00 m㎡

2.4 - 2.8 mm

9.6 kg/km

300 / 500 V

2000 V

 

Typical Applications

 

01low-voltage-switchgear-and-distribution-panel-secondary-wiring-the-4-x-od-bend-lets-a-300-500-v-wire-fold-into-a-shallow-duct

Low-voltage switchgear and distribution panel secondary wiring
Distribution panel secondary wiring; the 4 x core Ø bend lets a 300 / 500 V wire fold into a shallow duct.

02industrial-machine-tool-push-button-control-boxes-push-button-and-indicator-circuits-turned-behind-a-shallow-front-plate-on-a-class-5-conductor

Industrial machine tool local operator and push-button control boxes
Push-button and indicator circuits inside a machine control box, turned behind a shallow front plate on a class 5 conductor.

03industrial-luminaire-and-lighting-circuit-conduit-installation-protective-lead-inside-enclosed-luminaires-and-trunking

Industrial luminaire and lighting circuit conduit installation
Protective lead inside enclosed luminaires and trunking, self-extinguishing to DIN EN 60332-1-2 and IEC 60332-1.

04automated-wire-harness-subcontract-high-speed-assembly-cells-boxed-at-100-m-for-bench-and-field-work-or-on-spool-for-a-cut-strip-crimp-line

Automated wire harness subcontract high-speed assembly cells
Boxed at 100 m for bench and field work, or on spool and drum in several capacities for a cut-strip-crimp line.

 

Why Specify H05V-K

 

Why panel builders and control systems integrators standardize on H05V-K for cabinet secondary circuits:

 

Panel-wire property

What it means on site
Harmonised construction to DIN EN 50525-2-31 The document a European panel drawing names, so the wire matches what the drawing calls for.
Class 5 bare copper to DIN VDE 0295 Fine strands route round a DIN-rail terminal without the spring-back a solid core gives you.
PVC TI1 insulation, 4 x core Ø fixed bend Thin-wall insulation that still carries the flame and dielectric duties of the three standards, so more conductors fit the same duct.
Seventeen colour options, thirteen RAL-numbered A colour fixed by RAL number is the same colour on the next reel, which is what makes a wire schedule usable across builds.
Three packaging forms 100 m boxed for bench and field work, spool and drum in several capacities for longer runs and machine feeding.
Self-extinguishing to DIN EN 60332-1-2 and IEC 60332-1 The flame duty the range is tested to, on a compound that is also cadmium-free and silicone-free.

 

Frequently Asked Questions

 

Q: How does H05V-K differ from H07V-K?

A: Voltage and range. H05V-K is rated 300/500 V U0/U and covers 0.5, 0.75 and 1.0 mm² with a 2000 V test; H07V-K is rated 450/750 V, runs from 1.5 up to 240 mm² and is tested at 2500 V. Both are PVC single cores to the same harmonised family, so the choice is the circuit, not the construction.

Q: Why does this range stop at 1.0 mm²?

A:Because that is the harmonised size table for this type. Above 1.0 mm² the same duty is served by H07V-K, which starts at 1.5 mm² and runs to 240 mm² at 450/750 V.

Q: Can I get green or yellow?

A: Only where the safety regulations of the installation permit them. Green is additionally allowed for the identification of luminous decorative chains. Both colours exist in the article schedule, so the restriction is on use, not on availability.

Q: How is a two-colour wire ordered?

A: All two-colour combinations of the recommended single colours are allowed, and each cross-section has one article number for the two-colour build. Quote the base and the ring colour in the order notes - the article number fixes the cross-section, not the pair.

Q: How is the wire supplied?

A: In three forms: a 100 m cardboard box, a plastic spool and a cardboard drum. The spool and the drum come in several capacities, so the length per reel is fixed with the order.

Q: Can it be installed outdoors?

A: No. The range is specified for installation inside equipment, as a protective lead for luminaires, and in dry rooms, production halls, switchgear and distribution equipment, in conduit, and under or on plaster. Outdoor exposure is not part of that list.

 

Hot Tags: helukabel h05v-k single core hook-up wire, China helukabel h05v-k single core hook-up wire suppliers

Harmonised Wire Ratings

 

Rated voltage

Conductor

Temperature, fixed

Test voltage

Harmonised sizes

300/500 V AC

Class 5 fine bare copper

−30 °C to +80 °C

2000 V AC

0.5 – 1.0 mm² (Harmonised)

 

Panel Wire Ratings & Process Data

 

Electrical & mechanical baseline parameters

Parameter

Standard specification

Regulatory & harmonized standards

Certified to CENELEC European HAR standards, DIN EN 50525-2-31, DIN VDE 0285-525-2-31, and IEC 60227-3

Conductor construction

Bare copper strands, fine-stranded to DIN VDE 0295 class 5, BS 6360 class 5, and IEC 60228 class 5

Insulation formulation

Special lead/cadmium-free PVC insulation compound type TI1 to DIN VDE 0207-363-3 / DIN EN 50363-3

Flame retardancy rating

Self-extinguishing and flame retardant to IEC 60332-1, DIN EN 60332-1-2, and DIN VDE 0482-332-1-2

Specific insulation resistance

High dielectric resistance; minimum 10 Mohm x km at 20 C operating temperature

Environmental compliance

Free from cadmium, silicone, and paint-wetting impairment substances; fully CE compliant

Installation scope limitation

Designed for installation inside equipment enclosures, conduit tubes, or plaster conduits; prohibited for external direct mechanical exposure

 

Harmonisation and Approval Basis

 

Conductor DIN VDE 0295 class 5 / IEC 60228 class 5 | Harmonized single-core wire DIN VDE 0285-525-2-31 / DIN EN 50525-2-31 | International standard IEC 60227-3 | Flame retardance IEC 60332-1 / DIN EN 60332-1-2 | Low Voltage Directive 2014/35/EU

 

Filtering Sizes, Colours and Packaging

 

Part-number filtering — filter by the three calibrated cross-sections across 17 colour options, then switch packaging column between the 100 m box, the spool and the bulk drum.

 

H05V-K Part-Number Schedule by Packaging

 

Complete part-number schedule across all 3 H05V-K conductor cross-sections and 17 standardized colors, covering 100m dispenser boxes, plastic spools, and continuous bulk drums:

Cardboard Box Packaging (100m Pull-Out Dispenser Box)

01 H05V-K 100 m cardboard box part-number table article numbers by insulation colour and cross-section two-column layout

 

Plastic Spool Packaging (Multi-Capacity Reel)

02 H05V-K plastic spool part-number table article numbers by insulation colour and cross-section two-column layout

 

Cardboard Drum Packaging (High-Capacity Barrel for Automated Lines)

03 H05V-K cardboard drum part-number table article numbers by insulation colour and cross-section two-column layout

 

Send Inquiry