The RS485 cable is the shielded twisted-pair RS485 cable specified for the RS-485 communication protocol, and it is aimed at the two places that protocol turns up: complex industrial automation control networks and building automation networks. The same construction covers both ends of the duty range - a short RS485 serial cable between two devices inside a cabinet, an RS485 to RS485 cable in the simplest case, and a long RS485 bus cable running across a plant are the same shielded twisted pair, rated against the same window. A segment of that sort rarely runs on its own, so the construction puts aluminium foil and a tinned copper braid over two twisted pairs of stranded tinned copper insulated in foamed PE, and closes the whole thing in a purple PVC jacket. The characteristic impedance is 100–120 Ω over 1 to 10 MHz, the rated voltage is 300 V, and flame retardancy meets IEC 60332-1, with good resistance to external electromagnetic interference.
Typical Applications




Why Choose the RS485 Cable
Two pairs, four wires
The part number 2X2X24AWG/7 gives two pairs of 24 AWG conductors stranded 7 ways - four wires, identified as white / brown and green / yellow. The two-pair layout is the arrangement the RS-485 protocol is normally laid on, and it is the four-wire RS485 form. One conductor size is carried across the range.
100–120 Ω at 1–10 MHz
The characteristic impedance is 100–120 Ω across 1 to 10 MHz - the twisted-pair window the RS-485 protocol is designed for. Rated voltage is 300 V with a 2000 V/min (AC) test level, and the working range is −40 °C to +80 °C.
Foil plus braid
The shield is aluminium foil and tinned copper braid in a single layer. It is the element behind the cable's resistance to external electromagnetic interference, which is what an RS485 run sharing a route with power cable needs.
Purple RAL 4005 jacket
The outer jacket is PVC in purple at RAL 4005, so the bus run is identified by colour on a route it shares with power and control cable.
Frequently Asked Questions
Q: Which protocol is this cable specified for?
A: The RS-485 communication protocol, known in parallel as EIA-485, is the protocol this item is rated for, and it is what makes the cable an RS 485 communication cable rather than a general multi-core. The two network types it serves are complex industrial automation control networks and building automation networks.
Q: What is the characteristic impedance of an EIA-485 cable?
A: 100–120 Ω over 1 to 10 MHz, the characteristic impedance of the twisted pair.
Q: Is this an RS485 2 pair cable, and how many wires does it carry?
A: Two pairs, four wires in total. The part number 2X2X24AWG/7 gives two pairs of 24 AWG conductors stranded 7 ways, identified as white / brown and green / yellow - the two-pair RS485 arrangement the protocol is normally laid on, which is the four-wire RS485 form. One conductor size is carried across the range.
Q: Is this an RS485 shielded cable?
A: Yes. The shield is aluminium foil and tinned copper braid in a single layer, and it is the element behind the cable's ability to resist external electromagnetic interference.
Q: Can it be used as a Modbus 485 cable?
A: The cable is specified against the RS-485 communication protocol, which is the physical link Modbus RTU traffic is carried over, so a Modbus RTU RS485 cable is specified on the same shielded twisted pair and the same 100–120 Ω window. The rating is RS-485: no Modbus-specific test is claimed for this cable.
Q: Can it be used as an RS232 RS485 cable, or for RS422 and PROFIBUS?
A: No - the rating is for RS-485 only. No RS232 RS485, RS422/485 or PROFIBUS figures are given for this cable; segments of those kinds are specified against their own impedance and voltage data.
Q: Can it be supplied with an RS485 connector fitted?
A: Yes - as a finished harness rather than as a connector supplied on its own. The same cable is assembled to the drawing with the termination called for, whether that is a DB9 or an RJ45 shell, a terminal block or the customer's own housing, and the cable and the assembly are quoted in one document.
Hot Tags: rs485 cable, China rs485 cable suppliers
Electrical and Transmission Ratings
| Parameter | Value |
| Rated voltage | 300 V |
| Test voltage | 2000 V/min (AC) |
| Characteristic impedance | 100–120 Ω (1–10 MHz) |
| Conductor DC resistance (20 °C) | ≤95 Ω/km |
| Flame retardancy | Meets the requirements of IEC 60332-1 |
| Protocol | Complies with the RS-485 communication protocol |
| Transmission | Superior transmission performance with good resistance to external electromagnetic interference |
Product Structure
| Layer | RS485 Cable |
| ① Conductor | Stranded tinned copper |
| ② Insulation | Foamed PE |
| ③ Pair colours | White / brown and green / yellow |
| ④ Shield | Aluminium foil and tinned copper braid |
| ⑤ Outer jacket | PVC |
| ⑥ Jacket colour |
Purple (RAL 4005) |
Installation and Environmental Limits
| Parameter | Value |
| Minimum bending radius - fixed installation | 10 × OD |
| Minimum bending radius - flexing | 15 × OD |
| Temperature range | −40 °C to +80 °C |
| Duty | Fixed applications and occasional movement |
| Core identification | Up to 5 cores by insulation colour; above 5 cores white numbers, or to customer requirement |
| Jacket colour | Purple (RAL 4005) |