HELUKABEL JZ-500 Control Cable

HELUKABEL JZ-500 Control Cable
Details:
JZ-500 flexible PVC control cable for fixed installation and occasional free movement, 300/500 V, 0.5-185 mm², 2-100 cores. Six variants including JZ-500 black, the shielded JZ-500 C black and the tear-resistant JZ-500 PUR.

Standards & Compliance
DIN EN 50525-2-51 (PUR: DIN EN 50525-1) | DIN VDE 0295 cl. 5 | DIN VDE 0293 core ID | IEC 60332-1-2 | CE 2014/35/EU

Quick Specs
300/500 V | 0.5-185 mm², 2-100 cores | 7.5 × OD / 4 × (C black 10 × / 5 ×) | −40 to +80 °C fixed | 4000 V test
Send Inquiry
Download
Overview
Technical Specifications
Part Numbers
Part Number & specification Verification | Availability & Lead Time Confirmation

Xiamen Kabasi Electric Co., Ltd. is one of the most reliable manufacturers and suppliers of helukabel jz-500 control cable in China. If you're going to buy bulk durable cables made in China, welcome to get pricelist from our factory. All customized cables are with high quality and competitive price.

 

Introduction to the JZ-500 Range

 

JZ-500 is a 300/500 V fixed-installation flexible control cable built on bare copper conductors to DIN VDE 0295 class 5 with special PVC insulation. It is intended for flexible routing under medium mechanical stress, where the cable moves freely but carries no tensile load and is not forced into a guided motion. A single family absorbs the site variables through six interchangeable variants: base grey PVC; black with UV resistance; orange for interlock identification; COLD down to −30 °C mobile; C black with tinned copper braid for EMC margin; and PUR for tear and coolant-emulsion resistance. With 2–100 cores, 0.5–185 mm² and AWG equivalents listed alongside five-digit article numbers, sheath, temperature and screening are settled in one selection round.

 

Select Between the Six JZ-500 Variants

 

Variant comparison

Item

JZ-500

JZ-500 black

JZ-500 orange

JZ-500 COLD

JZ-500 C black

JZ-500 PUR

Sheath material

Special PVC TM2

Special PVC TM2

Special PVC TM2

Low-temp special PVC

Special PVC TM2

Full PU TMPU

Sheath colour

Grey RAL 7001

Black RAL 9005

Orange RAL 2003

Black RAL 9005

Black RAL 9005

Grey RAL 7001

Core insulation

PVC Z7225

PVC Z7225

PVC Z7225

PVC YI4

PVC Z7225

PVC TI2

Core marking

Black / white

Black / white

Orange / black

Black / white

Black / white

Black / white

Mobile temp.

-15 to +80 C

-15 to +80 C

-15 to +80 C

-30 to +80 C

-10 to +80 C

-15 to +80 C

Bending radius

7.5x / 4x

7.5x / 4x

7.5x / 4x

7.5x / 4x

10x / 5x

7.5x / 4x

Size range (mm²) 0.5-185 0.5-35 1.0-2.5 0.5-6 0.5-35 0.5-16

Copper braid

None

None

None

None

approx. 85 %

None

Radiation resistance

80 Mrad

80 Mrad

80 Mrad

80 Mrad

80 Mrad

100 Mrad

Outdoor / UV

Not for outdoor

Yes

Not for outdoor

Outdoor yes / UV not stated

Yes

Yes, outdoor

 

Select by site condition

Site condition

Select

Why

Outdoor, UV exposure

JZ-500 black

Black PVC sheath is UV-tested; electrical data identical to the base type

Ambient down to -30 °C

JZ-500 COLD

Low-temperature flexible sheath extends the mobile limit to -30 °C

VFD, servo and EMC-sensitive circuits

JZ-500 C black

Tinned copper braid with approx. 85 % coverage, coupling resistance max. 250 Ω/km

Coolant and cutting-fluid exposure

JZ-500 PUR

Full PU TMPU sheath resists tearing and coolant emulsions, 100 Mrad radiation resistance

Interlock circuits requiring identification

JZ-500 orange

Orange cores with black numerals follow the EN 60204-1 / VDE 0113-1 practice for live interlock circuits

Routine routing inside control cabinets

JZ-500 (base type)

The base build: same electrical and temperature data as black and orange

 

Typical Applications

 

01machining-and-cutting-fluid-environment-cnc-machining-centre-cutting-a-block-with-coolant-flooding-the-work-zone-and-tool-holder

Machining and cutting-fluid environment - JZ-500 PUR
Cutting fluid is thrown across a machine tool all day, and the full polyurethane TMPU sheath is why this build is listed for tool and equipment manufacturing and steel plants under demanding conditions.

02vfd-and-servo-surroundings-drive-cabinet-with-drive-modules-and-orange-motor-cables-landed-on-the-terminal-blocks-inside-a-machine-panel

VFD and servo surroundings - JZ-500 C black
On a machine frame where drives and the control cable share the same route, the tinned copper braid at approx. 85 % coverage is what carries the interference away - provided both ends are fully bonded, as the catalogue requires.

03cold-store-and-low-temperature-workshop-switchgear-cabinets-and-a-refrigeration-unit-along-a-concrete-plant-room-corridor

Cold stores and low-temperature workshops - JZ-500 COLD
A cold store or a low-temperature workshop is where the low-temperature PVC sheath earns its place: the mobile limit stays at -30 °C, the only one of the six builds below -15 °C.

04outdoor-equipment-and-exterior-routing-container-mounted-inverter-cabinet-with-heavy-cable-bundles-running-out-across-the-ground-at-a-desert-site

Outdoor equipment and exterior routing - JZ-500 black
Equipment mounted outside a building takes the black sheath, which is stated as UV-resistant and listed for outdoor routing - the grey base type is not.

 

Why Specify JZ-500

 

JZ-500 design point

What it changes on site

Six variants on one page

Sheath colour, low temperature, screening and chemical resistance compared in one pass instead of checking model by model

Verifiable electrical margin

4000 V test voltage, min. 8000 V breakdown voltage and min. 20 MΩ·km insulation resistance, matching the catalogue item by item

EMC option available

Tinned copper braid with approx. 85 % coverage and coupling resistance max. 250 Ω/km for VFD and servo surroundings

Low temperature and outdoor covered

COLD reaches -30 °C for mobile installation; black, COLD, C black and PUR are suitable for outdoor routing

Delivery aligned to assembly

Every size is metre-marked and cut to length, so cable and harness processing can ship together and offcuts stay minimal

 

Screen Termination & Shield-Bond Practice (JZ-500 C black)

 

This section applies only to JZ-500 C black, the single shielded variant on this page. The five unscreened variants are not covered here: their green-yellow earth core serves protective earthing only and is not a substitute for a screen. The practice below is written around the screening figures given by the catalogue - approx. 85 % coverage, coupling resistance max. 250 Ω/km, core/screen withstand test voltage 2000 V, bending radius 10 x OD (mobile) / 5 x OD (fixed) and a mobile-installation temperature limit of -10 °C.

Bond the screen at both ends. The catalogue requires the screen of the finished cable to be fully and completely contacted on both ends; without that bond, the 85 % braid coverage does not turn into real interference immunity.

Prefer a 360-degree clamp. Crimp or clamp the braid over the full circumference with a shield clamp or metal ring instead of leading the braid to a terminal with a single wire. A long pigtail raises the high-frequency impedance of the screen and gives away the EMC advantage the C black variant was specified for.

Never share a crimp with a conductor. The core/screen withstand voltage is 2000 V, well below the 4000 V between cores, so the braid must not enter the same crimp barrel or the same terminal as a conductor.

Respect bending radius and temperature together. Leave a transition length for the screen so the cable exits the terminal without falling below 10 x OD; the -10 °C mobile limit also means the cable should not be bent cold.

Choose single-ended or double-ended bonding deliberately. Base the decision on the potential difference between the cabinet earth and the machine earth; where single-ended bonding is used, insulate the unbonded end so it cannot touch the enclosure by accident.

Verify continuity afterwards. Confirm a low-resistance path from the screen to the earth bar, and never use the screen as a PE conductor where power and signal cables share a route.

 

Frequently Asked Questions

 

Q: How do JZ-500 and JZ-500 black differ?

A: Conductor, insulation, voltage class and temperature range are identical; only the sheath differs. The base type uses grey PVC (RAL 7001); black uses black PVC (RAL 9005) and is UV-tested, so it can be routed outdoors. Choose black when the installation has to match black harnesses or exterior routing; for ordinary cabinet wiring the base type is sufficient.

Q: How should the screening performance of JZ-500 C black be assessed?

A: The variant applies a tinned copper braid over the cores with approx. 85 % coverage and a coupling resistance of max. 250 Ω/km, with a core/screen withstand test voltage of 2000 V. The trade-offs are a bending radius of 10 x OD mobile and 5 x OD fixed, and a mobile temperature limit of -10 °C. Both cable ends must be fully and completely bonded, otherwise the EMC benefit drops sharply; see section 6 for the practice.

Q: How do I choose between JZ-500 PUR and PURö-JZ?

A: Both use a full polyurethane TMPU outer sheath, so the decision comes down to the duty. For machining duty dominated by coolant emulsions and cutting fluids, JZ-500 PUR resists emulsions better and reaches 100 Mrad radiation resistance. For duty dominated by mineral oil immersion where a lower mobile temperature is needed, PURö-JZ uses oil-resistant PVC TI2 core insulation with a mobile limit of -20 C, and the catalogue notes that it helps the cores slide inside the sheath under external stress.

Q: What do the G and x part-number suffixes mean?

A: G denotes a green-yellow earth core (3 cores and above); x denotes no earth core, which corresponds to the OZ design in the catalogue. Both part numbers share the same outer diameter, weight and copper weight for a given size, so the choice is purely about the earth core.

Q: Can the cable be used in a cable carrier or continuous flexing?

A: Only under the conditions the catalogue states. The range is described as suitable for flexible applications that must withstand medium mechanical stress, move freely, carry no tensile load and are not forced into a guided motion, and the catalogue also notes that it can be used in a cable carrier under specific conditions. Where continuous reciprocating flexing is planned, send the travel distance, acceleration and cycle rate so the construction can be checked against those conditions, or so we can recommend a drag-chain rated alternative.

Q: How are samples and volume deliveries scheduled?

A: Selection and proposal confirmation are returned within 2 working days and standard volume delivery stays within 15 days, with an order range of 10-5,000 sets. Lead time for samples and non-standard sizes is confirmed at quotation against the size and quantity. Cables can be processed to a customer-nominated brand or supplied as an alternative solution.

 

 

Hot Tags: helukabel jz-500 control cable, China helukabel jz-500 control cable suppliers

Ratings Common to All Six JZ-500 Variants

 

Voltage class

Conductor

Temperature, fixed

Dielectric test

Size range

300/500 V

Class 5 bare copper

−40 °C to +80 °C

4000 V

0.5 – 120 mm² (2–100 cores)

 

Electrical, Mechanical & Sheath Parameters

 

Common specifications (all six variants)

Item

Value

Conductor

Bare copper, fine strands; to DIN VDE 0295 class 5, BS 6360 class 5, IEC 60228 class 5

Core identification

To DIN VDE 0293: black cores with continuous white numerals (orange variant: orange cores with continuous black numerals)

Stranding

Cores stranded in layers at optimum lay length

Earth conductor

Green-yellow earth core in the outer layer (3 cores and above); on the orange variant the JZ design includes it, the OZ design does not

Rated voltage U0/U

300 / 500 V

Test voltage

4000 V (C black: core/core 4000 V, core/screen 2000 V)

Breakdown voltage

min. 8000 V

Insulation resistance

min. 20 MΩ·km

Flame retardance

To DIN VDE 0482-332-1-2, DIN EN 60332-1-2, IEC 60332-1 (equivalent to DIN VDE 0472 part 804, test method B)

Material declaration

Cadmium-free, silicone-free, free from substances that impair paint wetting

Length

Metre-marked; any custom length available

 

Variant-specific parameters

Item

Difference

Outer sheath

Special PVC TM2 (DIN VDE 0207-363-4-1 / DIN EN 50363-4-1); COLD uses low-temperature flexible special PVC; PUR uses full polyurethane TMPU (DIN EN 50363-10-2)

Core insulation

Z7225 (base / black / orange / C black); YI4 (COLD); TI2 (PUR)

Mobile-installation temperature limit

-15 °C (base / black / orange / PUR); -30 °C (COLD); -10 °C (C black)

Minimum bending radius

7.5x / 4x (base / black / orange / COLD / PUR); 10x / 5x (C black)

Screen

Tinned copper braid, approx. 85 % coverage; coupling resistance max. 250 Ω/km (C black only)

Radiation resistance

Up to 80 Mrad; PUR up to 100 Mrad

Chemical and weather resistance

PUR is highly resistant to coolant emulsions; black / COLD / C black / PUR may be used outdoors

 

Standards and Approvals Applied

 

Conductor DIN VDE 0295 class 5 / BS 6360 class 5 / IEC 60228 class 5 | Control cable DIN VDE 0285-525-2-51 / DIN EN 50525-2-51 (JZ-500 PUR: DIN VDE 0285-525-1 / DIN EN 50525-1) | Core identification DIN VDE 0293 | Flame retardance DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1 | PVC outer sheath DIN VDE 0207-363-4-1 / DIN EN 50363-4-1 | PUR outer sheath DIN EN 50363-10-2 (PUR variant only) | Low Voltage Directive 2014/35/EU

 

Filtering the JZ-500 Part-Number Schedule

 

Part-number filtering — search by five-digit article number, filter by core count (2–100) and cross-section (0.5–120 mm²), or switch variant between the six sheaths; AWG equivalents are carried in the same row.

 

JZ-500 Part-Number Tables

 

AWG conversion

The table below gives the AWG equivalents marked in the catalogue against nominal cross-sections. AWG is an approximation and the actual cross-section is the mm² value; the part-number tables repeat the AWG column so drawings in imperial units can be checked directly. Sizes of 150 mm² and above are listed in kcmil in the catalogue.

 

Nominal mm²

AWG

Nominal mm²

AWG

0.5

20

0.75

19

1

18

1.5

16

2.5

14

4

12

6

10

10

8

16

6

25

4

35

2

50

1

70

2/0

95

3/0

120

4/0

150 / 185

300 / 350 kcmil

 

Standard part-number tables

The tables cover 2, 3, 4, 5 and 7 cores in 0.5 to 2.5 mm². Each size exists as G (with green-yellow earth core, 3 cores and above) or x (without earth core, the OZ design); outer diameter, copper weight and total weight are identical for both. The full range of 2 - 100 cores up to 120 mm² is available on request.

 

JZ-500 Standard Size

01 JZ-500 standard sizes part-number table G and x article numbers two-column layout003

 

JZ-500 Black Standard Sizes

02 JZ-500 black standard sizes part-number table G and x article numbers two-column layout

 

JZ-500 Orange Standard Sizes

03 JZ-500 orange standard sizes part-number table G and x article numbers two-column layout

 

JZ-500 COLD Standard Sizes

04 JZ-500 COLD standard sizes part-number table G and x article numbers two-column layout


JZ-500-C Black Standard Sizes

05 JZ-500-C black standard sizes part-number table G and x article numbers two-column layout


JZ-500 PUR Standard Sizes

06 JZ-500 PUR standard sizes part-number table G and x article numbers two-column layout

 

Send Inquiry