YSLCY - 300/500 V Shielded PVC Control Cable

YSLCY - 300/500 V Shielded PVC Control Cable
Details:
YSLCY is the 300/500 V screened PVC control cable that the trade orders as a cy cable. Bare flexible stranded copper to GB/T 3956, PVC/D insulation, a polyester tape over the cores, a tinned copper braid and one PVC/ST9 sheath: the screen is bought without a second sheath.
Standards & Compliance
HD 21.13 and GB/T 5023 | GB/T 3956 conductor | PVC/D insulation, PVC/ST9 sheath | GB/T 18380.12 flame retardant
Quick Specs
300/500 V | 70 °C conductor | Polyester tape, tinned copper braid, PVC/ST9 sheath | 6 x OD fixed / 13 x OD moving
Send Inquiry
Download
Overview
Technical Specifications
Part Numbers
Part Number & specification Verification | Availability & Lead Time Confirmation

Xiamen Kabasi Electric Co., Ltd. is one of the most reliable manufacturers and suppliers of yslcy - 300/500 v shielded pvc control cable in China. If you're going to buy bulk durable cables made in China, welcome to get pricelist from our factory. All customized cables are with high quality and competitive price.

 

Lead Paragraph

 

YSLCY control cable is the screened single-sheath build of the PVC control range, and the trade orders it as a cy cable. The construction reads from the inside out: bare flexible stranded copper to GB/T 3956, PVC/D insulation, a polyester tape wound over the cores, a tinned copper braid, and one PVC/ST9 outer sheath, rated 300/500 V with a 70 °C conductor. The point of the tape is mechanical: it holds the braid in shape when the cable is stripped and keeps the braid wires off the insulation, so the screen can be fitted without adding an inner sheath. That is what separates this build from the double-sheath version of the same rating.

 

What the Tape Does Under the Braid

 

A braid is a mesh, and a mesh moves. Wound straight over soft PVC insulation, it spreads at a cut end, pushes into the wall under bending, and leaves loose strands that have to be dressed before the gland is closed. A polyester tape wound over the cores first gives the braid a firm cylinder to sit on: the strands keep their lay, the cut end stays square, and the braid can be trimmed back to a clean ring for the earthing clamp.

 

The tape also fixes the electrical geometry. It sets a defined distance between the braid and the insulated cores along the whole length, which is what makes the screen behave consistently rather than only where the cable happens to be tight. And because the tape is thin, the finished diameter stays close to the unscreened build of the same size - the screen costs less diameter than a second extruded sheath would.

 

 

Typical Applications

 

Supply and control on one route

The range allows the screened cable to be connected directly to a power line, so one route can serve both instead of two separated ones.

 

A control circuit beside a drive output

Where a control circuit shares an enclosure with a drive output or a switching device, the braid gives the interference a defined path to earth.

 

A screening requirement written into the drawing

Where the drawing already calls for a screen, the open question is not whether to screen but which build to put under it.

Occasional Movement, Not Continuous Bending

 

Screening changes the duty the cable can take. A braid stiffens the construction and concentrates flexing stress where the wires cross, so a screened control cable is not recommended for continuous bending. What it does take is occasional movement - machine tools, grinding machines and similar equipment that moves through a stroke rather than cycling all day. Where a route bends continuously, the unscreened member of the range carries that duty instead; the two duties are not interchangeable.

 

The Braid Is Tinned, and That Is a Termination Decision

 

The braid strands are tinned copper rather than plain copper. At the gland and at the earthing terminal the difference is practical: tinned strands resist oxidation in a damp cabinet and take solder without pre-cleaning, so a field termination stays repeatable. Plain copper braid oxidises at the cut end and needs abrasion before it will take a solder or a clamp reliably.

 

Frequently Asked Questions

 

Q: What is the difference between YSLCY and YSLYCY?

A: The layer under the braid. YSLCY carries a polyester tape between the insulated cores and the braid and closes with a single PVC/ST9 sheath. YSLYCY carries a PVC/ST5 inner sheath there and closes with the PVC/ST9 outer sheath, so its braid is enclosed between two sheaths. Rated voltage, conductor temperature, ambient range and bend radii are the same on both.

Q: Can this cable be used where the run moves?

A: For occasional movement. A screened control cable is not recommended for continuous bending, which is why the range is specified for machine tools and grinding machines rather than for drag chains.

Q: Can it be connected directly to a power line?

A: Yes. The range allows the screened cable to be connected directly to a power line, which is what makes a single route for supply and control wiring possible.

Q: Is the screen a foil, a braid, or both?

A: A tinned copper braid on its own. There is no aluminium foil layer in this construction; the tape under the braid is polyester and carries no electrical function.

Q: What does cy mean?

A: C denotes the copper braid screen and Y the PVC sheath, which is why the trade orders this construction as a cy cable or a cy control cable. The short form describes a construction family, not one maker product.

Q: What are the bend radius and the ambient range?

A: Fixed installation takes 6 x outer diameter at -10 to +70 °C; moving installation takes 13 x outer diameter at -5 to +70 °C. The maximum conductor operating temperature is 70 °C.

Q: Which standards does the cable reference?

A: HD 21.13 and GB/T 5023, with the conductor to GB/T 3956. Flame retardancy is tested to GB/T 18380.12 and oil resistance to GB/T 2951.5 and the referenced ASTM method.

Q: Is chemical resistance standard?

A: Oil resistance is stated on the range. Resistance to oil, cold, acid, alkali and solvents is an option, so it is named on the enquiry wherever the route passes a wash-down or fluid-contact area.

 

Hot Tags: yslcy - 300/500 v shielded pvc control cable, China yslcy - 300/500 v shielded pvc control cable suppliers

Electrical, Thermal and Fire Ratings

 

Parameter Rating
Rated voltage U0/U 300/500 V
Maximum conductor operating temperature 70 °C
Ambient temperature, fixed installation -10 to +70 °C
Ambient temperature, moving installation -5 to +70 °C
Minimum bend radius, fixed 6 x outer diameter
Minimum bend radius, moving 13 x outer diameter
Screen Tinned copper braid over a polyester tape
Continuous bending Not recommended
Flame retardancy Tested to GB/T 18380.12
Reference standards HD 21.13 and GB/T 5023; conductor to GB/T 3956

 

Construction

 

Element Material Note
Conductor Bare flexible stranded copper To GB/T 3956
Insulation PVC/D Cores insulated before the tape is applied
Separator Polyester tape Holds the braid lay and keeps strands off the insulation
Screen Tinned copper braid Takes solder and resists oxidation at the termination
Outer sheath PVC/ST9, single sheath Closes over the braid; colour and compound to order

 

Installation Reference

 

Installation Minimum bend radius Ambient temperature range
Fixed installation 6 x outer diameter -10 to +70 °C
Moving installation 13 x outer diameter -5 to +70 °C